Connect the PDU to your Ethernet LAN with a network cable (fig. 11, item 5).
Note:
Your changes to the network settings IP address, subnet mask and gateway will only be
saved if you confirm the gateway setting by clicking "Return". For example, if only the IP
address is confirmed with the "Return" key, and the menu for setting the subnet mask is
then exited by pressing the "Esc" key, the new IP address will not be saved.
6.2
Settings via the PDU website
Using a network cable, connect the device to your computer via the Ethernet interface (fig. 11,
item 5).
Note:
You may need to use a cross-over cable for this purpose.
Change your computer's IP address to any address within the range 192.168.0.xxx, e.g.
192.168.0.191. The default address 192.168.0.200 of the device must not be used.
Set the subnet mask to the value 255.255.255.0.
If applicable, switch off the proxy server in the browser to facilitate a direct connection to the device.
In the browser, enter the address http://192.168.0.200 (fig. 13, item 1). The login dialog for logging
in to the device will be displayed.
Log in with the username admin and the password admin (fig. 13, item 2).
In the left-hand section of the overview window (navigation area), click the Processing Unit entry
(fig. 13, item 3), and in the right-hand section (configuration area), click the Configuration tab
(fig. 13, item 4).
In the Network group box, click on the TCP/IP button (fig. 13, item 5).
Note:
The following sections describe in detail how to make the setting for the IPv4 protocol.
Further notes regarding the TCP/IP configuration can be found in section 1.1.
In the TCP/IP Configuration window, change the device's IP address in the IPv4 Configuration
group box to an address permitted in the network (fig. 13, item 6).
If necessary, correct the settings for the subnet mask and the gateway.
Alternatively, select the "DHCPv4" setting instead of "Manual" for automatic IP allocation.
Click on the Save button to change your settings.
Change the network settings of your computer to its original values for the IP address and the subnet
mask.
Disconnect the network cable from your computer.
Connect the PDU to your Ethernet LAN with a network cable.
For any required software updates, please visit www.rittal.com or contact Rittal Service (see section 9).
6.3
Connection of sensors
Up to four of the following CMC sensors may be connected to the PDU:
– Temperature sensor (7030.110)
– Temperature/humidity sensor (7030.111)
– Infrared access sensor (7030.120)
– Vandalism sensor (7030.130)