4.2 - Mounting of chain manual override
1
S1
S2
5
WIRING
Three-phase SIMUBOX motors have been made to be exclusively wired with 1.5 mm² diameter cables for the power
supply connection and with 0.75 mm² diameter cables for the command connection.
Attach the cables to prevent contact with moving parts.
- The installer must ensure that the installation of the motorization complies with the electrical installation instructions
in force in the country of commissioning.
- Always make a loop on the power cable to prevent water penetration into the actuator.
- Cables passing through a metal wall must be protected and insulated by a sleeve or sheath.
- The motor casing must be connected to a rigid conduit.
- Use the traction stop.
- The connection of the power supply conductors must only be made after installing the motor on its support.
- Cables have to be stripped on 8 mm.

Installation diagram:

U
V
W
Fdc
Fdc
Fdc
Fdc
Secu
Secu
S1
S1
S2
S2
Mot
Mot
2
3
S1
S2
Refer to SD510 control manual
SAFETY BRAKE
4
There are 2 auxiliary contacts available
which allow, for example, to know if the door
is in open or closed position.
Outputs are made on a 3 terminal connector
which is fixed on the cover plate.
Outputs of auxiliary contacts on 3 terminal
connector :
SD510
Type of output : dry contacts normally open
Capacity : 1A under 24Vdc
1. Remove the chain cover by
unscrewing the 4 screws.
2. Install the chain.
3. Pass the chain links in the
chain guide and in the notched
wheel by introducing them in.
4. Replace the cover.
• 1 terminal Ri S1 for S1
• 1 terminal Si Com pour common
• 1 terminal Ri S2 for S2
i
Traction stop has to be used.
Secu Mot inputs have to be wired in
order to operate the motor.
4/5
EN