3-phase Type 2 Surge Protector
DS440 series
DS440-400
• Compact 3-phase Type 2
• In : 20 kA
• Imax : 40 kA
• Common/Differential mode
• Pluggable module
• Remote signaling contact (option)
• Complies with EN 61643-11, IEC 61643-11 and UL1449 ed.4
Characteristics
CITEL Model
Description
Network
Connection mode
AC system
Max. AC operating voltage
Temporary Over Voltage (TOV)
Charasteristics - 5 sec.
Temporary Over Voltage (TOV)
Charasteristics - 120 mn
Temporary Over Voltage N/PE (TOV HT)
Residual current
- Leakage current at Uc
Follow current
Nominal discharge current
- 15 x 8/20 µs impulses
Max. discharge current
-max. withstand @ 8/20 µs by pole
Protection level CM/DM*
@In (8/20µs) and @ 6kV (1.2/50µs)
Admissible short-circuit current
Associated disconnectors
Thermal disconnector
Fuses
Installation ground fault breaker
Mechnical characteristics
Dimensions
Connection to Network
Disconnection indicator
Remote signaling of disconnection
Spare unit
Mounting
Operating temperature
Protection rating
Housing material
Standards compliance
Certification
Part number
*Note: CM = Common mode (L/PE or N/PE)/ DM = Differential mode (L/N)
**Note: Rating in compliance with NF C15-100 art. 534.1.5.3. An order to increase service continuity, higher rating can be used. For further information, please consult product instructions.
67
44
60.8
DS440-400
DS440-230
Compact 3-phase+N Type 2 surge protector - 230/400 V - Pluggable
230/400 V 3-phase
230/400 V 3-phase
L/PE and N/PE
L/PE and N/PE
IT
TN
Uc
440 Vac
255 Vac
UT
580 Vac withstand
335 Vac withstand
UT
770 Vac disconnection
440 Vac disconnection
UT
-
-
Ipe
< 1 mA
< 1 mA
If
None
None
In
20 kA
20 kA
Imax 40 kA
40 kA
Up
1.8 kV
1.25 kV
Isccr 10000 A
10000 A
internal
Fuses Type gG - 50 A**
Type "S" or delayed
see diagram
by screw terminals: 1.5-10mm² (L/N) or 2.5-25mm² (PE)
4 mechanical indicators
4 mechanical indicators
Option DS440S-400 :
Option DS440S-230 :
output on changeover
output on changeover
contact
contact
DSM440-400
DSM440-230
Symmetrical rail 35 mm (EN60715)
-40/+85°C
IP20
Thermoplastic UL94-V0
IEC 61643-11 / EN 61643-11 / UL1449 ed.4
EAC
311402
311702
DS440S-xxx
L1
L2
L1
L2
L3
N
Ft
Ft
90
MI t°
9
36
DS440 S-xxx/G
DS440-230/G
230/400 V 3-phase
L/N and N/PE
TT-TN
255 Vac
335 Vac withstand
440 Vac disconnection
1200 V/300A/200 ms
withstand
None
None
20 kA
40 kA
1.5/1.25 kV
10000 A
3 mechanical indicators
Option DS440S-230/G :
output on changeover
contact
DSM440-230/G and
DSM440-230/GPE
311722
Imax
Imax
40 kA
40 kA
DS440S-xxx/G
L3
L1
L2
L3
N
Ft
Ft
Ft
Ft
Ft
MI t°
MI
MI t°
C
V : High energy varistor
GSG : Specific GDT
Ft : Thermal fuse
C : Remote signaling contact
t° : Thermal disconnection system
MI : Disconnection indicator
« » = CT1 configuration (common mode)
«G» = CT2 (common and differential mode)
Operating voltage
«S» = Remote signal option
Imax 40 kA
4 protected poles
DS440-120
DS440-120/G
Compact 3-phase+N Type 2 surge protector -
120/208 V - Pluggable
120/208 V 3-phase
120/208 V 3-phase
L/PE and N/PE
L/N and N/PE
TN
TT-TN
150 Vac
150 Vac
180 Vac withstand
180 Vac withstand
230 Vac disconnection
230 Vac disconnection
1200 V/300A/200 ms
-
withstand
< 1 mA
None
None
None
20 kA
20 kA
40 kA
40 kA
0.9 kV
1.5/0.9 kV
10000 A
10000 A
4 mechanical indicators
3 mechanical indicators
Option DS440S-120 :
Option DS440S-120/G :
output on changeover
output on changeover
contact
contact
DSM440-120/G and
DSM440-120
DSM440-120/GPE
311602
311622
N
GSG
C
52

Publicité

loading

Sommaire des Matières pour Citel DS440 Serie

  • Page 1 «S» = Remote signal option • Remote signaling contact (option) Imax 40 kA • Complies with EN 61643-11, IEC 61643-11 and UL1449 ed.4 4 protected poles Characteristics CITEL Model DS440-400 DS440-230 DS440-230/G DS440-120 DS440-120/G Compact 3-phase+N Type 2 surge protector -...
  • Page 2 Technical Data Installation N110203d 2000 m max. 6500 ft max. INSTALLATION INSTRUCTIONS - NOTICE D'INSTALLATION -40/+85°C max. NOTICIA DE INSTALACIÓN - INSTALLATIONSHINWEISE -40/+185°F max. ISTRUZIONI PER L'INSTALLAZIONE IP20 INSTRUCOES DE INSTALACAO - MONTÁŽNÍ NÁVOD indoor use only - 安装指导书 Main switchboard or sub-panel AC Network AC surge protector - Parafoudre Basse Tension...
  • Page 3 查看最新文件请登陆公司网站。 下使用; - Svodič přepětí se smí používat pouze v souladu se svými technickými parametry a podle těchto www.citel.fr - 请根据不同的电源网络制式选用浪涌保护器,参见 montážních pokynů. www.citel.de Table 1; - Svodiče přepětí je zapotřebí zvolit a používat tak, aby www.citel.us...

Ce manuel est également adapté pour:

Ds240 serieDs440-400Ds440-230Ds440-230/gDs440-120Ds440-120/g