mundoclima MH-70-V9 Manuel D'installation Et L'utilisauter page 38

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

8) Checks to electrical devices
Repair and maintenance to electrical components shall include initial safety checks
and component inspection procedures. If a fault exists that could compromise
safety, then no electrical supply shall be connected to the circuit until it is
satisfactorily dealt with. If the fault cannot be corrected immediately but it is
necessary to continue operation, an adequate temporary solution shall be used.
This shall be reported to the owner of the equipment so all parties are advised.
Initial safety checks shall include:
• That capacitors are discharged: this shall be done in a safe manner to avoid
possibility of sparking;
• That there no live electrical components and wiring are exposed while charging,
recovering or purging the system;
• That there is continuity of earth bonding.
3. Repairs to sealed components
1) During repairs to sealed components, all electrical supplies shall be disconnected from
the equipment being worked upon prior to any removal of sealed covers, etc. If it is
absolutely. Necessary to have an electrical supply to equipment during servicing, then
a permanently operating form of leak detection shall be located at the most critical
point to warn of a potentially hazardous situation.
2) Particular attention shall be paid to the following to ensure that by working on electrical
components, the casing is not altered in such a way that the level of protection is
affected. This shall include damage to cables, excessive number of connections,
terminals not made to original specification, damage to seals, incorrect fitting of glands,
etc.
Ensure that apparatus is mounted securely.
Ensure that seals or sealing materials have not degraded such that they no longer serve
the purpose of preventing the ingress of flammable atmospheres. Replacement parts
36

Publicité

Table des Matières
loading

Table des Matières