rough framing
EN
3.3
minimum clearance to combustible enclosures
1" [25mm] minimum all sides for vertical venting sections.
* 72" (182.8cm) min.
for typical application
84" (213cm) min.
for recess application
* Refer to "venting requirements" and "venting installation" sections.
** Clearances within the enclosure may be higher (refer to "minimum framing dimensions" section).
A
1" [25mm] minimum tous les côtés pour les sections
d'évacuation verticale.
22
W415-2949 / D / 05.19.22
Non-combustible
material
12"
9 1/4"
[305mm]
E36
60"
Combustible
Non-combustible
Brick
3"
[76mm]
to top
3"
min.
2"
[51mm] to
sides / bottom
Firestop
assembly
(not supplied)
1" [25mm]
E42
Combustible
Incombustible
Brique
3"
[76mm]
vers le
haut
3"
0" [0mm] if non-combustible
finishing material is used
such as brick and stone.
A
+ rise
64"
0" [0mm] si les matériaux
sont inombustible, comme
de la brique et de la pierre.