Télécharger Imprimer la page

Mitsubishi Electric TRANE NTXMMX48A182B Serie Manuel D'installation page 18

Publicité

Les langues disponibles

Les langues disponibles

6. Electrical work
6.6. Address setting
Switch address setting
Unit
Outdoor
Address
Switch
SWU2
SWU1
range
51 - 100
setting
Branch address + 50
Note: 1. Branch box address
When setting the address, use a number within the range 1–50.
Ex. The set address is (47) and there are 5 indoor units (A, B, C, D, and E).
If A: (47), B: (48), C: (49), D: (50), and E: (51), E is incorrect because it exceeds 50.
Ex1. Outdoor + Branch <1> (Indoor A, B, C, D, E) + Branch <2> (Indoor A, B, C)
Outdoor
address
(51) *
1
Ex2. Outdoor + Branch <1> (Indoor A, C, E) + Branch <2> (Indoor A, C, E)
Outdoor
address
(51) *
1
en
17
Address
SW12
1 - 50
• According to the set address (for example, 01), the ad-
dresses for the connected indoor units are set sequentially
(for example, 02, 03, 04, and 05).
SW1
1
2
3
4
ON ON ON ON ON
Port
A
B
C
D
Address
01
02
03
04
Branch-Box <1>
address (01) *
2
SW1 1, 2, 3, 4, 5 ON
(01) = A-port
(02) = B-port
(03) = C-port
(04) = D-port
(05) = E-port
Branch-Box <2>
address (06) *
3
SW1 1, 2, 3 ON
SW1 4, 5
OFF
(06) = A-port
(07) = B-port
(08) = C-port
Branch-Box <1>
address (01) *
2
SW1 1, 3, 5 ON
SW1 2, 4
OFF
(01) = A-port
non
B-port
(02) = C-port
non
D-port
(03) = E-port
Branch-Box <2>
address (04) *
3
SW1 1, 3, 5 ON
SW1 2, 4
OFF
(04) = A-port
non
B-port
(05) = C-port
non
D-port
(06) = E-port
Branch Box
Port
ON
OFF 1
SW11
• Specify whether indoor units are connected to each
port (A, B, C, D, and E).
5
SW1
Port
E
Indoor units are connected ON
(SW11, 12)
Indoor units are not connected OFF
05
(sequential numbers)
*1 Outdoor address
Branch Box <1> start address + 50 = 01 + 50 = 51
*2 Branch Box <1>
A-port address = Start address = 01
B-port address = Start address + 1 = 02
Indoor
C-port address = Start address + 2 = 03
Indoor
D-port address = Start address + 3 = 04
Indoor
E-port address = Start address + 4 = 05
Indoor
Indoor
*3 Branch-Box <2>
Branch Box <2> start address
= Branch Box <1> oldest start address + 1
= 05 + 1 = 06
A-port address = Start address = 06
B-port address = Start address + 1 = 07
Indoor
C-port address = Start address + 2 = 08
Indoor
Indoor
*1 Outdoor address
Branch Box <1> start address + 50 = 01 + 50 = 51
*2 Branch-Box <1>
A-port address = Start address = 01
B-port address
C-port address = Start address + 1 = 02
Indoor
D-port address
E-port address = Start address + 2 = 03
Indoor
Indoor
*3 Branch-Box <2>
Branch Box <2> start address
= Branch Box <1> oldest start address + 1
= 03 + 1 = 04
A-port address = Start address = 04
B-port address
Indoor
C-port address = Start address + 1 = 05
D-port address
Indoor
E-port address = Start address + 2 = 06
Indoor
Connection Setting
A
B
C
D
E
ON: Indoor connect
OFF: No connection
2
3
4
5
6
*
SW1
*SW1-6 not use
1
2
3
4
5
(6)
A
B
C
D
E
(not use)
no connection
no connection
no connection
no connection
Indoor
None
There are no
address settings
for the indoor
units.

Publicité

loading