Télécharger Imprimer la page

Mitsubishi Electric TRANE NTXMMX48A182B Serie Manuel D'installation page 16

Publicité

Les langues disponibles

Les langues disponibles

6. Electrical work
6.5. Wiring of main power supply and equipment capacity
Schematic Drawing of Wiring (Example) (Fig. 6-3)
<When Power Is Supplied from the Outdoor Unit>
A
208/230 V AC, 60 Hz
<When Power Is Supplied Separately>
A
208/230 V AC, 60 Hz
Thickness of Wire for Main Power Supply and On/Off Capacities
<When power is supplied separately>
Model
NTXMMX48A182✱✱
Outdoor Unit
NTXMPH✱✱A1✱2✱✱
NTXMMX60A182✱✱
Branch Box
<When power is supplied from the outdoor unit>
Model
NTXMMX48A182✱✱
Outdoor Unit
NTXMPH✱✱A1✱2✱✱
NTXMMX60A182✱✱
Branch Box
*1. Please follow applicable federal, state, or local codes to prevent potential leakage/electric shock. Or install a ground fault interrupt for the prevention of leakage and
electric shock.
IMPORTANT
If a current leakage breaker is used, it should be compatible with higher harmonics as this unit is equipped with an inverter. The use of an inadequate breaker
can cause the incorrect operation of inverter.
*2. Use copper supply wires. Use the electric wires over the rating voltage 300 V.
Total operating current of the indoor unit
en
F0 = 15 A or less *2
F0 = 20 A or less *2
F0 = 30 A or less *2
Apply to IEC61000-3-3 about max. permissive system impedance.
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + ... + {V1 × (Quantity of Type7)/C}
15
B
L1/L2
B1/B2
L1/L2
GR
L1/L2
B
208/230 V AC, 60 Hz
L1/L2
GR
Minimum Wire Thickness
Power Supply
(mm
[AWG])
2
Main Cable*2
Ground
5.3 [AWG10] 5.3 [AWG10]
8.4 [AWG8]
8.4 [AWG8]
208/230 V AC,
60 Hz
8.4 [AWG8]
8.4 [AWG8]
Minimum Wire Thickness
(mm
[AWG])
Power Supply
2
Main Cable*2
Ground
8.4 [AWG8]
8.4 [AWG8]
13.3 [AWG6] 13.3 [AWG6]
208/230 V AC,
60 Hz
13.3 [AWG6] 13.3 [AWG6]
Minimum wire thickness (mm
Main Cable
Branch
2.1/14
2.1/14
3.3/12
3.3/12
5.3/10
5.3/10
C
S1/S2/S3
D
S1/S2/S3
D
S1/S2/S3
D
C
A Switch (Breakers for Wiring and Current Leakage (if you use))
S1/S2/S3
D
B Outdoor Unit
S1/S2/S3
C Branch Box
D
D A-Control indoor unit
S1/S2/S3
E Pull Box
E
A
C
S1/S2/S3
L1/L2
S1/S2/S3
S1/S2/S3
Fig. 6-3
Breaker for
Breaker for Current Leakage
Wiring*1
(if you use)
30 A
30 A 30 mA 0.1 sec. or less
40 A
40 A 30 mA 0.1 sec. or less
40 A
40 A 30 mA 0.1 sec. or less
Refer to installation manual of Branch Box.
Breaker for
Breaker for Current Leakage
Wiring*1
(if you use)
40 A
40 A 30 mA 0.1 sec. or less
45 A
45 A 30 mA 0.1 sec. or less
50 A
50 A 30 mA 0.1 sec. or less
Refer to installation manual of Branch Box.
/AWG)
Ground-fault interruper *1
2
Ground
(if you use)
2.1/14
15 A current sensitivity *3
3.3/12
20 A current sensitivity *3
5.3/10
30 A current sensitivity *3
C
S1/S2/S3
D
D
L1/L2
S1/S2/S3
D
D
S1/S2/S3
D
Minimum circuit
Maximum rating of over
ampacity
current protector device
29 A
44 A
36 A
44 A
36 A
45 A
Minimum circuit
Maximum rating of over
ampacity
current protector device
35 A
50 A
42 A
50 A
46 A
55 A
Local switch (A)
Breaker for wiring
Capacity
Fuse
(NFB)
15
15
15
20
20
20
30
30
30

Publicité

loading