Installer Settings
Settings
80
80
Resume Schedule
75
75
Basic
Time
Humidity
Away
Home
Away
Vacation
Fan
65
72
BACK
Furnace Settings
Installer Settings
80
80
Resume Schedule
75
75
Furnace
AC/HP
Thermostat
Air Handler
Defaults
Home
Away
Warning! These settings are to be used
by a qualified HVAC contractor ONLY
72
65
BACK
Furnace Settings
80
80
LED Display Orientation
Upflow
Resume Schedule
Furnace Blower Off Delay
75
75
90 secs.
Hi Heat Airflow Adjust
None
Lo Heat Airflow Adjust
None
G Input Fan Control
Home
Away
Off
Aux #1 Config
N.O.
Off
Aux #2 Config
N.O.
Off
65
72
BACK
> Return to Table of Contents
To enter the Installer Settings menu, select Menu > Settings, then tap and hold on
"Installer" on the bottom right of the screen for five seconds.
44%
44%
Installer
Go to Menu > Settings > Installer (tap and hold) > Furnace.
44%
44%
LED Display Orientation – Flips the furnace's LED diagnostic display so it is
readable in the upflow or downflow position.
Furnace Blower Off Delay – 90 (default), 120, 150, 180 seconds. Amount
of time the blower will run after a furnace heating call has ended.
44%
44%
Hi Heat Airflow Adjust – This setting will adjust the heat gain of the second
MORE
stage or high stage of the two-stage furnace. There are five optional settings to
choose from. The default is 'None'.
• Highest Airflow: Will decrease the second stage Midpoint heat rise -12˚F
by increasing the CFM even higher
• Higher Airflow: Will decrease the second stage Midpoint heat rise -7˚F by
increasing the CFM
• None: Nominal CFM and heat rise across the furnace
• Lower Airflow: Will increase the second stage Midpoint heat rise +7˚ by
lowering the CFM
• Lowest Airflow: Will increase the second stage Midpoint heat rise +12˚
by lowering the CFM even lower
Lo Heat Airflow Adjust – This setting will adjust the heat gain of the first
stage or the low stage of the two-stage furnace. There are five optional settings
to choose from. The default is 'None'.
• Highest Airflow: Will decrease the first stage Midpoint heat rise -12˚F by
increasing the CFM even higher
• Higher Airflow: Will decrease the first stage Midpoint heat rise by -7˚F by
increasing the CFM
• None: Nominal CFM and mid heat rise across the furnace
• Low Airflow: Will increase the first stage Midpoint heat rise +7˚ by
lowering the CFM
• Lowest Airflow: Will increase the first stage Midpoint heat rise +12˚ by
lowering the CFM
G Input Fan Control – Off (default), Low, Medium Lo, Medium, Medium
High, High: airflow to run if the G terminal is activated. To be used for add-on
accessories (like ventilators) that are wired to the furnace G terminal and wish to
run the blower.
EcoNet
Smart Thermostat User Guide
®
28