Télécharger Imprimer la page

Deltadoors LiftMaster my Q AA250EVK Manuel D'installation Et D'opération page 19

Publicité

Les langues disponibles

Les langues disponibles

7. PROGRAMMING
Speed Motors 1 & 2 in CLOSE Direction
Speed Motor 1 and 2 in CLOSE direction allows closing speed adjustment compa-
red to the speed set during Learning phase. Password must be entered to access
this function.
Standard speed (Default)
+10%
+20%
+30%
7.7.15f Soft-Stop Speed
Soft-Stop Speed function allows adjustment of the Soft-Stop speed compared to
default values set during Learning phase. Soft-Stop speed is 50% of the standard
speed as per default setting. Standard speed change impacts the Soft-Stop speed.
Password must be entered to access this function.
Standard speed (Default)
-10%
-20%
-30%
8. BATTERY BACKUP
Battery Back-Up Mode
2 Optional 12V, 2.2Ah lead batteries SKU 490EV (optional, not included) can be mounted inside the E-Box. Follow the manual of SKU 490EV for exact installation proce-
dure. A Flashing lamp (if mounted) will flash 2 seconds every 10 minutes indicating BBU mode and power loss. Control board will switch into stand-by mode with active
radio receiver accepting radio control device commands only. All other accessories and peripheral devices will not be functioning.
When in Battery Back-up mode, myQ Smartphone Control and wireless myQ devices will be disabled. Full charged battery capacity shall support up to ~20 cycles at a
rate of 2 per hour. After 24 hours of BBU mode the battery shall provide power for 1 complete opening and closing cycle. Please note that only the specified battery can
be use. Use of any other battery leads to loss of warranty and loss of liability of LiftMaster for any related damages resulting from use of unspecified batteries.
9. ERROR CODES
Error
LED
code
Press transmitter, but no gate
E0
movement
Gate do not close, but can
E1
Gate can close when it is at
E2
open limit, but cannot open
when it's at close limit.
Press transmitter, but no gate
E3
Press transmitter, but no gate
E4
+50%
-10%
-20%
-50%
+10%
+20%
Issue
AP is set to 00
1) IR1 is not connected, or wire is cut.
2) IR1 wire is shorted out or reverse connected.
open.
3) IR1 is not aligned or blocked for a moment.
1) IR2 is not connected, or wire is cut.
2) IR2 wire is shorted out or reverse connected.
3) IR2 is not aligned or blocked for a moment.
1) IR3 is not connected, or wire is cut.
2) IR3 wire is shorted out or reverse connected.
movement.
3) IR3 is not aligned or blocked for a moment.
1) Safety edge is not connected with 8.2kohm
resistor.
movement.
2) Safety edge wire is shorted out.
3) Safety edge is pressed.
7.8 Factory Default
Factory default function resets control board to the original factory set-ups. All set-
tings, including limit settings, will be erased. LED display will show "E0". Program-
med remote controls will remain learned. If Remote control accessories need to be
erased refer to the respective Radio Controls Programming section of this manual.
no reset (Default)
reset to the factory default settings
7.9 Finish and Exit
To exit the programming phase and save all changes,
move to FE function and press "P" button. The control board will go into Stand-by
mode and is ready to work.
There are also other ways to exit the programming and save settings:
• Press and hold "P" button for 5 seconds
• Wait 3 minutes after the last changes in the programming for automatic exit
Possible reason
18
Solution
Check if AP is set to 00. If yes, change to correct application setting.
1) Check if IR1 is not connected, or wire is cut.
2) Check IR1 connection, change wires if needed.
3) Align IR transmitter and receiver to make sure both LED is on,
instead of blinking. Make sure there is nothing hanging on gate that
may cause IR blocking.
1) Check if IR2 is not connected, or wire is cut.
2) Check IR2 connection, change wires if needed.
3) Align IR transmitter and receiver to make sure both LED is on,
instead of blinking. Make sure there is nothing blocking the IR.
1) Check if IR3 is not connected, or wire is cut.
2) Check IR3 connection, change wires if needed.
3) Align IR transmitter and receiver to make sure both LED is on,
instead of blinking. Make sure there is nothing hanging on gate that
may cause IR blocking in short time.
1) Check if the 8.2 kOhm safety edge is properly connected or if the
8.2 kOhm resistor is installed.
2) Check safety edge wires and replace wire if needed.
3) Check if safety edge is pressed.

Publicité

loading