BLOCK DIAGRAM
PROGRAMMING
• Loop Link is a communications interface that is needed for programming MBT 9110
• For programming please refer to the drawing below and the help functions in PReset
• Loop Link is not approved for communication with modules installed in hazard ous (EEx) areas
1
2
MBT 9110
Mechanical specifications
6 | AQ40924351751001-000101
–
–
MBT 9110
–
084Z7440, 084Z7441
*
L oop
5909 - USB
L ink
5905 - RS232
Mounting of sensor wires
Wires must be mounted
between the metal plates
© Danfoss | Climate Solutions | 2022.03
APPENDIX
ATEX Installation drawing
MBT 9110 - 084Z7441
ATEX Certificate
DEKRA 20ATEX0105X
II 1 G Ex ia IIC T6...T4 Ga
Marking
II 2 D Ex ia IIIC Db
Standards
EN 60079-0:2017, EN 60079-11:2011, EN 60079-15:2010, EN 60079-7:2017
Hazardous area
Zone: 0, 1, 2, 21, 22, M1 / DIV.1, DIV.2
T4: -40 ≤ Ta ≤ 85 °C
T6: -40 ≤ Ta ≤ 60 °C
Terminal: 3,4,6
6
Uo: 27 VDC
Io: 7 mA
5
Po: 45 mW
4
Lo: 35 mH
3
Co: 90 nF
Terminal: 1,2
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10 H
Ci: 1.0nF
INSTALLATION NOTES
SAFETY INSTRUCTIONS
For safe installation of MBT 9110 084Z 7441 the following must be observed. The module shall only be Installed by qualified
personnel who are familiar with the national and international laws, directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
In a potentially explosive gas atmosphere, the transmitter shall be mounted in an enclosure in order to provide a degree of
protection of at least IP20 according to EN60529.
If the transmitter is installed in an explosive atmosphere requiring the use of equipment of category 1G and if the enclosure is
made of aluminium, it must be installed such, that even in the event of rare incidents, ignition sources due to impact and friction,
sparks are excluded; if the enclosure is made of non-metallic materials, electrostatic charging shall be avoided.
For installation in a potentially explosive dust atmosphere, the following instructions apply:
The transmitter shall be mounted in a metal enclosure form B according to DIN43729 that is providing a degree of protection of
at least IP6X according to EN60529, that is suitable for the application and correctly installed.
Cable entries and blanking elements shall be used that are suitable for the application and correctly installed.
For an ambient temperature ≥ 60 °C, heat resistant cables shall be used with a rating of at least 20 K above the ambient
temperature.
The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a dust layer with a thickness up to 5 mm.
Danfoss A/S
Danfoss Sensing Solutions
DK 6430 Nordborg Denmark
Phone +45 7488 2222