Télécharger Imprimer la page

Samsung DVE45N5300 Serie Manuel D'utilisation page 14

Masquer les pouces Voir aussi pour DVE45N5300 Serie:

Publicité

Les langues disponibles

Les langues disponibles

Installation requirements
Ducting requirements
Weather hood
type
No. of 90°
elbows
0
1
2
3
NOTE
* Use a 4-inch (10.2 cm) diameter rigid aluminum or galvanized steel duct.
If you integrate the dryer's vent system with an existing exhaust system:
• Make sure the exhaust system meets all applicable local, state, and national regulations.
• Verify you are not using flexible plastic duct.
• Make sure to check for and remove all lint buildup from inside the existing ducts.
• Confirm the duct is not kinked or crushed.
• Make sure the exhaust hood damper opens and closes freely.
Manometer measurements
The static pressure in any exhaust system must not exceed 0.83 inches of water column
or be less than 0. Note that these values are measured with the dryer running with a
manometer presented to the exhaust duct that connects to the dryer. The dryer tumbler
must be empty and lint filter clean.
14
English
DV5500M_DC68-03381G-06_EN.indd 14
Recommended
4" (10.2 cm)
Rigid
80 ft. (24.4 m)
68 ft. (20.7 m)
57 ft. (17.4 m)
47 ft. (14.3 m)
Use only for short-run installation
2.5" (6.4 cm)
Rigid
74 ft. (22.6 m)
62 ft. (18.9 m)
51 ft. (15.5 m)
41 ft. (12.5 m)
2019-06-03
2:47:26

Publicité

loading