QUICK START GUIDE
Carry out the ground connection of the inverter before carrying out any electrical connection. The SUNWAY M XS is
supplied with a three-wire cable for the connection to the grid. First connect the yellow-green wire to the ground of the
electrical system external to the inverter. The yellow-green wire is internally connected to the Protective Earth of the
circuit.
CONNECTION TO THE GRID
Connect the SUNWAY M XS to the grid using the snap-in connectors supplied with the product. Connect the line (L),
neutral (N) and protective earth (PE).
DANGER
Always remove voltage before operating on the grid.
CAUTION
PROTECTION AGAINST DIFFERENTIAL CURRENT – The inverters of the SUNWAY M XS series are compatible with
external RCDs of type A according to the regulations in force, because, by construction, they cannot generate DC
differential currents, even under single fault conditions.
Always install a MCCB to protect the electric circuit. The minimum trip threshold of the RCD shall be 100 mA for every
inverter installed.
WIRING DIAGRAM
10/30