Télécharger Imprimer la page

Haier MVHR072ME2CA1 Manuel D'installation page 21

Publicité

Les langues disponibles

Les langues disponibles

INSTALLATION INSTRUCTIONS
Allowing Piping Length and Drop Between Indoor and Outdoor (cont.)
2. Allowable piping length and drop
between indoor and outdoor unit.
Outdoor 1
The outdoor is more than one unit.
When the distance between outdoors(L1, L3) is over 6-9/16 ft., the oil trap must be set (upright
projecting pipe, 7-7/8 in. high), as the figure :
Outdoor 2
L2
Below 6-9/16 ft.
L1
Over 7-7/8 in.
Over 7-7/8 in.
L3<32-13/16 ft.
L1+L3<32-13/16 ft.
L2+L3<32-13/16 ft.
Note:
V1---V4: VP unit
A---F: indoors (coling / heating selection possible)
G---H: indoors (cooling only)
31-5000573 Rev. 2
Outdoor 3
Outdoor is only one
L5
Outdoor 3
L4
Below 6-9/16 ft.
L5
L3
L11
V1
L12 L13
A
The connection sketch of stop valves and pipes
1
2
3
4
1
2
A
B
C
A
B
C
1 ---- High pressure gas pipe stop valve
2 ---- Low pressure pipe stop valve
3 ---- Liquid pipe stop valve
4 ---- Charge valve
Detail view for stop valve of HR unit
High pressure gas pipe
Low pressure gas pipe
L6
L11
L16
V1
L17
L15
L14
L12 L13
B
C
A
L6
L7
L8
L9
L16
L18
L20
V2
V3
V4
L10
L22
L17
L19
L21
L15
L14
E
F
G
B
C
D
H
H2
3
4
1
2
3
4
A
B
C
C
B
A
A ---- High pressure gas pipe
B ---- Low pressure pipe
C ---- Liquid pipe
Service port
Liquid pipe
Charge value
L7
L8
L9
L18
L20
V2
V3
V4
L22
L10
L19
L21
D
E
F
G
H
H2
Liquid pipe
Indoor Unit
Gas pipe
Liquid pipe
Connection
Indoor Unit
Kit
Gas pipe
Liquid pipe
Indoor Unit
Gas pipe
Liquid pipe
Indoor Unit
Gas pipe
21

Publicité

loading