Electrical connections
DISCONNECT POWER BEFORE
SERVICING THE PRODUCT. FAILURE TO DO SO
COULD RESULT IN DEATH OR ELECTRICAL
SHOCK.
General information
THE MODELS MAY BE POWERED
AT 240V OR 208V.
This cooktop does not require a neutral connection. If the
cooktop is to be completely enclosed in a cabinet, feed the
cooktop cable through the opening in the cabinet. Make the
electrical connection following the appropriate steps for your
installation.
Your cooktop must be connected to the proper electrical
voltage and frequency as specified in the table on the right.
Figure 12. Location of serial tag.
Connect with copper wire only
If the house has aluminum wiring, follow the procedure
below:
1. Connect the aluminum wiring to the copper wire by using
special connectors designed and Underwriters
Laboratories-listed for joining copper to aluminum. Follow
the electrical connector manufacturer's recommended
procedure.
2. Aluminum/copper connection must conform with local
codes and industry- accepted wiring practices.
Installation Instructions
7
The flexible conduit (supplied) 3 feet long (100 cm) located
at the right rear of the cooktop bottom box should be
connected directly to junction box. Do not cut the conduit. A
U.L - or CSA - listed conduit connector must be provided at
each end of the power supply cable (at the cooktop and at
the junction box.)
A time delay fuse or circuit breaker is recommended.
Do not ground to a gas pipe. Do not have a fuse in the
grounding or neutral circuit.
Fuse both supply (phase) lines.
IMPROPER CONNECTION OF
ALUMINUM HOUSE WIRING TO THE COPPER
LEADS CAN RESULT IN A SERIOUS PROBLEM.
Power Supply
Model
240V 60Hz
24"
6,0kW
25A
6,1kW
25,5A
National Fire Protection Association
Batter/march Park Quincy, Massachusetts 02269
A three-wire, single phase, 240 Volt 60 cycle electrical
system (properly circuit protected to meet Local Codes of
NFPA No.70) must be provided. Unit must be properly
grounded in accordance with local wiring code. The chart
below recommends the minimum circuit protector and wire
size if the appliance is the only unit on the circuit. If smaller
sizes of wire are used, the unit efficiency will be reduced
and a fire hazard may be created. It is advisable that the
electrical wiring and hookup be accomplished by a
competent electrician.
Approval
code
208V 60Hz
4,5kW
21,5A
514Y40NN
4,6kW
22A
514Y40IL