CU2 + ATEX
Technical data
CU2 RMEX(T)
Operating mechanism
Remote controlled damper with electrical, explosion proof
Description
rotary actuator (for zone 2/22)
Certifications
Classification
See installation manual of CU2 (NT-C2)
Free air passage
SL (dm²) = [ (W
- 45 (W
Mounting
In floor/ wall
Durability test
After 10.000 cycles the characteristics stay within the
declared limit values.
Safety position
Closed
Operation
Automatically: (only RMEXT- version) by melting of
the thermo-electric fuse at 72°C. Remote controlled by
interrupting the power supply.
Rearmation
Manual
Remote controlled
Unlocking
Cold unlocking possible
Installation direction
Horizontally or vertically
Air movement
Both Directions
Fire side
Random
Operating pressure
Max 500 Pa
Environment
For interior use
Nominal voltage
24...240 VAC/DC
Position indication
2 integral, potential free aux. switches, 2 x EPE
Degree of protection
IP66
Maintenance
Maintenance-free
Explosion proof
Ambient temperature: -10°C ≤ Ta ≤ 40°C
II3G IIC T6
II3D T80°C
Ambient temperature: -10°C ≤ Ta ≤ 50°C
II3G IIC T5
II3D T95°C
If the product is manipulated in any other way than described in this manual, Rf-Technologies will decline any responsibility and
the guarantee will expire immediately!
Explosion protected fire damper
-36) x (H
– 36)
nom
nom
- 36) ] 10 000
nom
CU2 EMEX(T)
Remote controlled damper with electrical, explosion proof
rotary actuator (for zone 1/2/21/22)
See installation manual of CU2 (NT-C2)
SL (dm²) = [ (W
-36) x (H
– 36)
nom
nom
- 45 (W
- 36) ] 10 000
nom
In floor/ wall
After 10.000 cycles the characteristics stay within the
declared limit values.
Closed
Automatically: (only EMEXT- version) by melting of the
thermo-electric fuse at 72°C. Remote controlled by
interrupting the power supply.
Manual
Remote controlled
Cold unlocking possible
Horizontally or vertically
Both Directions
Random
Max 500 Pa
For interior use
24...240 VAC/DC
2 integral, potential free aux. switches, 2 x EPE
IP66
Maintenance-free
Ambient temperature: -10°C ≤ Ta ≤ 40°C
II2G IIC T6
II2D T80°C
Ambient temperature: -10°C ≤ Ta ≤ 50°C
II2G IIC T5
II2D T95°C
K50-F
7