Factory reset
This button allows you to restore the device to factory settings by pressing it continuously for
more than 10 seconds.
Digital input
EN
Voltage free input. It can be used as a window contact, occupancy or similar to turn the AC unit
on/off if the input changes value.
By default it will be disabled and configured as "normally open."
It is recommended that the wiring of the digital inputs be routed through a separate conduit.
Reset of the device
Allows you to reset the device without removing any previously set configuration parameters.
Smart thermostat connection
Port that receives signals from smart thermostats via the GYW lines. In addition, the terminal
has another 3 pins for 24 Vac power supply (RH, RC, C).
You can link your smart thermostat account with the Airzone Cloud app. To do this, follow the
steps described in the
Once the connection is made, if there is no integration with a third-party account, it can be
configured if the control is carried out by the Airzone Cloud app or by the thermostat (by
default). In this case, it will work with the G (ventilation), Y (cooling) and W (heating) lines
following a control logic that will allow to adjust the setpoint temperature of the machine in an
approximate way to the setpoint temperature of the third party thermostat. As for the speed, it
will use the last one read by the equipment.
Power supply input
12 Vdc input that enables providing power to the Aidoo Pro device.
The 230 Vac - 12 Vdc power supply is supplied with the device.
6
Airzone Cloud app
Manual.
Smart
thermostat
INDOOR UNIT
Power supply
unit not
External power input for
smart thermostat
provided
(For smart