ENGLISH
1
2-Position
DIP Switch
Bonding Lug
Figure 9.
Wiring to a Controller
3.4
Pump DIP Switch Settings
The motor is equipped with an auto sensing power
circuit which eliminates the need for DIP switches
1 and 2. As shown in Figures 9, the 2-position DIP
switch serves the function of pump addressing when
using multiple pumps. If the pump is connected to a
JEP-R controller or iQPUMP01, DIP switches 3 and 4
must remain in the OFF position. If connecting to an
automation system that supports multiple pumps, use
the DIP switches (See Table 3) to set the address for the
pump and refer to the automation system's manual for
additional instructions.
NOTE
DIP switches 3 and 4 must only be used if your
Zodiac
Automation system does NOT have RS-485
®
auto-addressing capabilities.
Switch 3
Switch 4
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Table 3.
DIP Switch Settings
3.5
Auxiliary Relay Operation
Jandy pump model numbers ending with "2A" are
equipped with a terminal bar that provides user access to
two built-in Auxiliary Relays. The normally-open relays
are activated under certain operating conditions and
are intended to be used to control external devices that
require system water flow for proper functioning, such
as booster pumps, salt water chlorinators, etc.
See Figures 10 and 11 for compartment's location
details.
Jandy
Variable-Speed Pumps
®
Controller
(Rear View)
5 4 3 2 1
4 3 2 1
RS485
REMOTE CONTROL
4 3 2 1
2
3
4
1- 3/8" Threaded
2- 3/4" Threadless
3- 1/2" Threadless
4- 1/2" Threaded
Pump Address
PUMP 1 (Factory Default)
PUMP 2
PUMP 3
PUMP 4
|
Installation & Operation Manual
An access cover with Phillips-head screw must be
removed before proceeding.
Auxiliary Load Connection Requirements
ELECTRICAL SHOCK HAZARD
Due to the potential risk of fire, electric shock, or injuries
to persons, Jandy
Pumps and any auxiliary loads must
®
be installed in accordance with the National Electrical
Code
(NEC
), all local electrical and safety codes, and
®
®
the Occupational Safety and Health Act (OSHA). Copies
of the NEC may be ordered from the National Protection
Association, 1 Batterymarch Park, Quincy, MA 02169, or
from your local government inspection agency.
In Canada, Jandy Pumps must be installed in accordance
with the Canadian Electrical Code (CEC).
• The Auxiliary Load relay contacts are rated at
230V/115V, 11A RMS. Please ensure the requirements
of the equipment to be connected to the Auxiliary Load
do not exceed this rating.
3.5.1
Auxiliary Relay Operation
Characteristics
Auxiliary Relay contact activation is speed dependent.
Auxiliary Relay 1 has an activation speed of 1725 RPM
and Auxiliary Relay 2 has an activation speed of 2250
RPM.
3.5.2
Contact Closure
From a stopped condition, there is a three-minute delay
before the Auxiliary Relay contact is closed when the
motor speed reaches and maintains the activation speed.
Once the three minute run time criteria has been reached,
when going from an RPM below the activation speed to
an RPM above the activation speed, there is a 5-second
delay before the Auxiliary Relay contact is closed.
3.5.3
Contact Opening
When going from an RPM above the activation speed to
an RPM below the activation speed, the relay opening is
always immediate.
WARNING