FPS-T1U RACK INSTRUCTION MANUAL
FPS-T1U RACK SPECIFICATIONS
1
Number of power supply modules (*1)
2
Maximum output power
3
Input voltage / frequency range
4
Maximum input current (at 100/200Vac)
AC input connector
5
6
Output terminals
7
Remote sensing
8
Parallel operation
9
Series operation
10
Remote On/Off control
11
DC_OK signal
12
AC fail signal
13
Over Temperature alarm signal
14
Vout voltage trimming
15
Auxiliary power supply
16
Operating temperature
17
Storage temperature
18
Operating humidity
19
Storage humidity
20
Vibration
21
Shock
22
Applicable safety standards
23
Withstand voltage
24
Insulation resistance
25
Weight (Typ)
Size (W*H*D)
26
27
Warranty
Notes:
*1: The Output of all the FPS1000 modules are floating in the rack.
*2: For input voltage lower than 100Vac, maximum output power derated by 10% of the power rating.
*3: For cases where conformance to to various safety standards (UL, EN etc.) is required, to be described
as 100-240Vac (50/60Hz).
*4: Remote sensing can compensate up to 1V drop on each load wire.
*5: Not apllicable for units with I
*6: Factory default: ON/OFF_1 P.S. is on when AC is applied.
---
W
(*2)
(*3)
---
A
---
FPS-T1U :IEC inlet for each power supply module . FPS-T1U/P :None
---
(*4)
V
---
Possible. Up to 3 racks with max 8FPS 1000 units of the same voltage and current rating.
(*5)
---
Possible. Up to 3x FPS1000 units of the same voltage and current rating
Separate control for each FPS 1000 unit , By electrical signal or dry contact
(*6)
---
On/Off logic is user selectable. Refer to instruction manual.
Separate control for each FPS1000 unit, Open collector signal.
---
Separate control for each FPS1000 unit ,Open collector signal.
---
Separate control for each FPS1000 unit ,Open collector signal.
---
---
Possible, via separate control for each FPS1000 unit .Refer to Instruction Manual.
---
11.2~12.5VDC.Maximum output current:0.25A, for each FPS1000 unit.
---
---
---
---
---
---
---
Input-Output: 3000Vrms, 1min. Input-Ground: 2000Vrms, 1min. Output-Ground:
---
---
More than 100Mohm at 25°C and 70% RH. Output-Ground: 500Vdc
Kg
---
Yr
2
C bus option.
Maximum 3 x FPS1000 modules.
3000
85~265Vac continuous, 47~63Hz, Single phase
12.0/6.0 for each FPS1000 unit installed
Bus-bars.Refer to outline drawing.
Possible.
On when Vout >80% +/-5%. Max.sink current: 10mA
Refer to Instruction Manual
Refer to Instruction Manual
0~50°C: 100% load. Derate 2%/°C, 50°C to 60°C.
-30~85°C
10~90% RH, no condensation.
10~95% RH, no condensation.
Built to meet ETS 300 019
Built to meet ETS 300 019
UL60950-1, EN60950-1
1414Vdc, 1min.
3.7
440x44x351mm. Refer to Outline Drawing.
Two Years