7. Electrical work
7.6. Address setting
Switch address setting
Unit
Outdoor
Address
Switch
SWU2
SWU1
range
51 - 100
• According to the set address (for example, 01), the ad-
SW1
setting
Branch address + 50
Port
Address
Note: 1. Branch box address
When setting the address, use a number within the range 1–50.
Ex. The set address is (47) and there are 5 indoor units (A, B, C, D, and E).
If A: (47), B: (48), C: (49), D: (50), and E: (51), E is incorrect because it exceeds 50.
Ex1. Outdoor + Branch <1> (Indoor A, B, C, D, E) + Branch <2> (Indoor A, B, C)
Branch-Box <1>
address (01)
SW1 1, 2, 3, 4, 5 ON
Outdoor
address
(51)
*1
Branch-Box <2>
address (06)
SW1 1, 2, 3 ON
SW1 4, 5
Ex2. Outdoor + Branch <1> (Indoor A, C, E) + Branch <2> (Indoor A, C, E)
Branch-Box <1>
address (01)
SW1 1, 3, 5 ON
Outdoor
SW1 2, 4
address
(51)
*1
Branch-Box <2>
address (04)
SW1 1, 3, 5 ON
SW1 2, 4
Address
SW12
SW11
1 - 50
dresses for the connected indoor units are set sequentially
(for example, 02, 03, 04, and 05).
1
2
3
4
5
ON ON ON ON ON
A
B
C
D
E
01
02
03
04
05
*2
(01) = A-port
Indoor
(02) = B-port
Indoor
(03) = C-port
Indoor
(04) = D-port
Indoor
(05) = E-port
Indoor
*3
OFF
(06) = A-port
Indoor
(07) = B-port
Indoor
(08) = C-port
Indoor
*2
OFF
(01) = A-port
Indoor
non
B-port
(02) = C-port
Indoor
non
D-port
(03) = E-port
Indoor
*3
OFF
(04) = A-port
Indoor
non
B-port
(05) = C-port
Indoor
non
D-port
(06) = E-port
Indoor
Branch Box
Port
A
ON
OFF 1
• Specify whether indoor units are connected to each
port (A, B, C, D, and E).
SW1
Port
Indoor units are connected ON
(SW11, 12)
Indoor units are not connected OFF
(sequential numbers)
*1 Outdoor address
Branch Box <1> start address + 50 = 01 + 50 = 51
*2 Branch Box <1>
A-port address = Start address = 01
B-port address = Start address + 1 = 02
C-port address = Start address + 2 = 03
D-port address = Start address + 3 = 04
E-port address = Start address + 4 = 05
*3 Branch-Box <2>
Branch Box <2> start address
= Branch Box <1> oldest start address + 1
= 05 + 1 = 06
A-port address = Start address = 06
B-port address = Start address + 1 = 07
C-port address = Start address + 2 = 08
*1 Outdoor address
Branch Box <1> start address + 50 = 01 + 50 = 51
*2 Branch-Box <1>
A-port address = Start address = 01
B-port address
no connection
C-port address = Start address + 1 = 02
D-port address
no connection
E-port address = Start address + 2 = 03
*3 Branch-Box <2>
Branch Box <2> start address
= Branch Box <1> oldest start address + 1
= 03 + 1 = 04
A-port address = Start address = 04
B-port address
no connection
C-port address = Start address + 1 = 05
D-port address
no connection
E-port address = Start address + 2 = 06
Connection Setting
B
C
D
E
ON: Indoor connect
OFF: No connection
2
3
4
5
6
*
SW1
*SW1-6 not use
1
2
3
4
5
(6)
A
B
C
D
E
(not use)
Indoor
None
There are no ad-
dress settings for
the indoor units.
15