Télécharger Imprimer la page

Maxx Cold MXSF-23FD Manuel D'entretien, D'installation Et D'utilisation page 14

Publicité

Les langues disponibles

Les langues disponibles

OPERATION (Units Made After July 2018) (cont.)
2. MAIN FUNCTIONS
2.1 HOW TO SEE THE SET POINT
1. Push and immediately release the SET key, the set point will be showed;
2. Push and immediately release the SET key or wait about 5s to return to normal
visualization.
2.2 HOW TO CHANGE THE SETPOINT
1. Push the SET key for more than 2 seconds to change the Set point value;
2. The value of the set point will be displayed and the "°C" or "°F" LED starts blinking;
3. To change the Set value push the
or
arrows.
4. To memorize the new set point value push the SET key again or wait 10s.
2.3 HOW TO START A MANUAL DEFFROST
Push the DEF
key for more than 2 seconds and a manual defrost will start
2.4 TO LOCK THE KEYBOARD
1. Keep pressed for more than 3s the
and
keys.
2. The "OF" message will be displayed and the keyboard will be locked. If a key is pressed more
than 3s the "OF" message will be displayed.
2.5 TO UNLOCK THE KEYBOARD
Keep pressed together for more than 3s the
and
keys till the "on"
message will be displayed.
3. ALARM SIGNALLING
3.1. ALARM RECOVERY
Probe alarms P1" and "P2" start some seconds after the fault in the related probe; they automatically
stop some seconds after the probe restarts normal operation. Check connections before replacing the
probe. Temperature alarms "HA" and "LA" automatically stop as soon as the temperature returns to normal values.
Alarms "EA" and "CA" (with iF=bL) recover as soon as the digital input is disabled.
Page 14 of 58

Publicité

loading

Ce manuel est également adapté pour:

Select serieMxsf-49fd