Télécharger Imprimer la page

DRESSER ACTARIS GAS 800 Serie Mode D'emploi page 13

Soupape de surpression

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 14
General Information
The safety relief valve are used for low throughput (SRV
for leaking gas) and assembled after a gas pressure
regulator . It prevents the Safety Shut-Off Valve (SSV)
from responding to slight gas leakage of the regulator
actuator or to zero consumption .
Installation
• Check that the maximum inlet pressure of the
station isn't higher than the pressure PS of safety
relief valve .
• Arrange enough room for the serving of the regu-
lator .
Before installing the safety relief valve (SRV) in the
piping, the following must be checked:
• The upstream and downstream flanges must be paral-
lel so as to install the SRV without undue stress .
• The upstream piping must be cleaned from all im-
purities (sand, welding slag, etc . )
• The safety relief valve must be not visibly dam aged .
• The inlet and outlet chambers of the safety re lief
valve must be perfectly clean .
• Make sure that the direction of gas flow cor-
responds to the arrow on the safety relief valve body .
Installation position
• The installation position of SRV is freely selecta ble .
Relief-piping
• To realize sufficient safety distance of set points
on the gas-station, the following cross section of
relief-piping are to apply:
DN 20 up to 5 m relief-piping,
DN 25 or larger of more than 5 m relief-piping,
Service
• All work on the safety relief valve is to carry out only
in the pressure-free condition . The safety regula-
tions, in particular the accident prevention regula-
tion, as well as all other national rules and regulations
have to be considered:
• Valves on the upstream- and downstream side are to
closed .
• The pressure must be reduced by the relief valve
on the outlet side, up to zero level
Adjusting of SRV-set point
The safety relief valve is delivered according to the
specifications, specified in the purchase order . If the
adjusted relief pressure is to be changed, proceed as
follows:
• Remove the cap .
• The adjustment screw in the spring housing is to turn
clockwise, to increase the blow-off pres sure; anti-
clockwise, to decrease the blow-off pressure .
SRV
external hexagon
Caution!
When disassembling the safety
re lief valve, the loading spring is
to release before!
801
803
811
SW20
SW24
SW30
13

Publicité

loading

Ce manuel est également adapté pour:

Actaris gas 801Actaris gas 811Actaris gas 811rActaris gas 803