Charge time
Lifetime
The batteries have a life time expectancy of 4 years when maintained properly. Replace after that time!
Automatic emergency time selection
After installation and power up the driver will detect the battery and start the automatic detection process.
- During automatic detection, the indicator LED will light up with short green flashes.
- Between minimum 6 and maximum 30 seconds the TrustSight driver wi l l set the battery type (number of ceand will
set the emergency output power accordingly.
After that, the system is defined and fully operational. The battery type definition has influence on the performance
during the self-test and on the battery charge method. When the automatic battery detection process is disrupted,e.g. by
switching off the permanent mains, the detection process is stopped and the TrustSight emergency driver will go into
emergency mode with the lowest output power. At a next power up, the automatic detection process will start again.
Periodic testing
Periodic tests of emergency lighting luminaires must be performed according to EN5 0172 clause 7.2.3 and 7.2.4. Switch
on in the emergency mode each month by simulation of a failure of the supply to the normal lighting a period sufficient
to ensure that each lamp is illuminated. Twice per year, each luminaire shall be tested for its full rated duration (at least
3hrs).
For more information please consult the TrustSight Gen 3 Des ign in guide. The latest version is available online.
In case a self-contained emergency driver has been added, this is how to set the timers (IEC62034 (§6.3.2)):
DALI version:
Check IEC 62386 part 202.
PRO version:
The rst test is randomized. Then a xed schedule is maintained, there is no need
to set the timers or take special precautions when powering
BASIC version:
No timers available, only manual testing through the test button.
24.00
5/12