1.- Introduction
Refrigerator gas leak detection alarm to be used in refrigerated facilities designed to comply with standard
EN 378-3.
2.- Versions and references
MODEL
AKO-52201
AKO-52202
AKO-52210
AKO-52211
Detector for freon gases. Type A
AKO-52212
Detector for freon gases. Type B
AKO-52201
AKO-52202
DETECTOR
AKO-52211
R-134a, R-407C, R-410A, R-417A, R-409A, R-32
R-404A, R-507A, R-22, R-23, R-422D, R-422A, R-434A,
AKO-52212
R-437A, R-408A, R-403B, R-124, R-407A
* The pre-alarm and alarm levels can slighty differ from the values shown in the table depending
on the detected type of gas.
WARNINGS
- The alarm and detectors should be installed in a place protected from vibrations, water and corrosive
gases, where the ambient temperature does not exceed the value indicated in the technical data. The
station should be installed in a place where the regular presence of people who can alert to the
presence of alarms is guaranteed.
- To prevent false alarms, the detector should be installed away from:
Ÿ
Maintenance rooms where solvents, paints or refrigerator gases are handled.
Fruit ripening or storage rooms, as some fruits can emit gases.
Ÿ
Smoke outlets located in confined spaces (carbon dioxide, propane, LPG) or from engines,
Ÿ
generators or motorised machinery (fork-lift trucks, etc.).
Ÿ
Particularly damp areas or with the risk of getting wet.
Areas with strong ventilation.
Ÿ
- Do not paint the detector or place it near solvents or paints.
- Neither the alarm or gas detector are suitable for areas classified as potentially explosive.
DESCRIPTION
Alarm station + Detector
Alarm station + Detector
Alarm station
GASES IT DETECTS
DETECTOR INCLUDED
AKO-52211
AKO-52212
-
-
-
AKO-52210
10
POWER SUPPLY
90-260V~
50/60 Hz
-
AKO-52211
AKO-52212
PRE-ALARM
ALARM
500 ppm*
1000 ppm*