QS Link Wiring
(continued)
• System communication uses
IEC PELV/NEC
Class 2 wiring.
®
• Follow all local and national electrical
codes when installing IEC PELV/NEC
Class 2 wiring with line voltage/
LUTRON
mains wiring.
• Make all connections in the control
LUTRON
unit's wallbox.
• Wiring can be T-tapped or daisy-chained.
• 24 V- 100 mA IEC PELV/NEC
Note: The QS Timeclock provides
3 power draw units on the QS link.
For more information on PDUs, see
"Power Draw Units on the QS Link",
PN 369405 at www.lutron.com
LUTRON
Wire Sizes (check compatibility in your area)
QS Link Wiring Length
Less than 500 ft (153 m)
500 to 2000 ft
LUTRON
(153 to 610 m)
LUTRON
LUTRON
LUTRON
®
All manuals and user guides at all-guides.com
®
LUTRON
LUTRON
Class 2.
®
Daisy-Chain Wiring Example
QS Timeclock
Wire Gauge
Power (terminals 1 and 2)
1 pair 18 AWG (1.0 mm
)
2
Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm
Power (terminals 1 and 2)
1 pair 12 AWG (4.0 mm
)
2
Data (terminals 3 and 4)
1 twisted, shielded pair 22 AWG (0.5 mm
T-Tap Wiring Example
QS Timeclock
Energi Savr Node
Sivoia QS
smart panel
Sivoia QS
Shade
Energi Savr Node
Sivoia QS
Shade
Lutron Cable Part Number
GRX-CBL-346S (non-plenum)
GRX-PCBL-346S (plenum)
)
2
GRX-CBL-46L (non-plenum)
GRX-PCBL-46L (plenum)
)
2