PROGRAMMABLE LED INDICATOR 5514
• 4-digit LED indicator
• PC-programmable
• Scaling by front function keys
• 2 relay outputs
• Current / voltage or temperature input
• Front IP65 enclosure
IN GENERAL:
The 5514 with 2 relay outputs is designed for digital readout of current / voltage
or temperature signals.
The 5514 A1 with temperature input can measure signals from standard Pt100
and thermocouple sensors, and mV signals.
The 5514 A2 with current and voltage input can be programmed in ranges of max.
100 mA and 250 VDC and contains a transmitter supply.
As both types are galvanically separated, both grounded and floating signals can
be measured.
The 5514 is delivered fully-configured acc. to specifications. Alternatively, by way
of the programming kit Loop Link and a PC, you can configure the unit yourself.
By way of the front function keys, display readout, placement of decimal point,
and trip amplifiers can be scaled when activated in the software.
0 and 100% process calibration is possible by way of Loop Link.
INPUT TYPES FOR 5514 A1:
RTD input for Pt100 / Ni100 in temperature ranges acc. to IEC 751 and DIN
43760. By way of Loop Link, the cable resistance can be measured and compen-
sated at a 2-wire connection.
Automatic cable compensation at 3- or 4-wire connection.
Selectable sensor error detection.
Thermocouple input (TC) for standard thermocouples in temperature ranges
acc. to IEC 584, DIN 43710, or ASTM E988-90.
Internal CJC with Pt100 sensor in the terminal (optional - type 5914), external
CJC with Pt100 / Ni100 at 2-wire connection, or fixed CJC (thermostat box).
Selectable sensor error detection.
30
All manuals and user guides at all-guides.com
Resistance input for Ohmic resistance measurement, max. range 5000 Ω.
Automatic cable compensation at 3- or 4-wire connection.
mV input for DC voltage signals.
INPUT TYPES FOR 5514 A2:
Current input for signals of max. 100 mADC. The input is protected by a PTC
resistor.
Voltage input for signals of max. 250 VDC.
Auxiliary supply 20 VDC / 20 mA for supply of 2-wire transmitters.
Linearisation is possible acc. to your specifications.
DISPLAY:
4 red 14.2 mm LED digits. Max. readout ±9999 with selectable decimal point.
Scaling either by the programming kit Loop Link or the front keyboard. Rever sible
readout. If the input is outside the measurement range, the display shows either
"In.HI" or "In.LO".
For indicators with temperature input, sensor errors are indicated by "SEnS" in
the display. Test of display and LEDs is possible by the front keys. Access to
change of parameters can be blocked by a password. 2 green LEDs indicate the
tendency of the input signal.
RELAY OUTPUTS:
Are selected as either a make or a break function. The relays can be used as a trip
amplifier and / or sensor / cable error alarm for TC, RTD, and resistance inputs.
2 yellow front LEDs indicate the relay status. The relays can be set up with either
delayed on or off. Active relay can be selected for either an increasing or decrea-
sing signal. The arrow keys can be used for fast change of the setpoint.
SET-UP:
Loop Link contains PReset software, adapter box, cable etc.
The adapter box is galvanically isolated which protects the PC.
The communication is a two-way communication, which means that the present
set up including series / tag number can be retrieved from the indicator.
31