1.1 SEt1 - Setting of relay 1 setpoint.
Possible selections are 0...99.99%, or d-LO...d-HI in display units.
The setpoint is set in % of the input signal or in display units depending
on the selection in menu 4.3.
1.2 HYS1 - Setting of relay 1 hysteresis.
Possible selections are 0...99.99%, or 0...(d-HI) - (d-LO) in display units.
The hysteresis is set in % of the input signal or in display units depen-
ding on the selection in menu 4.3.
1.3 InC1 / dEC1 - Setting of active relay 1 for increasing / decreasing
input signal.
Possible selections are InC or dEC.
The relay functions
Normally Open (N.O.) and
(N.C.) are selected in the set-up program PReset and are sent to the
display.
1.4 dOn1 / dOF1 - Setting of delayed ON / OFF.
Possible selections are dOn or dOF.
If dOn has been selected, relay 1 will not be activated until after the
delay entered in menu 1.5.
If dOF has been selected, relay 1 will not be deactivated until after the
delay entered in menu 1.5.
If no time delay is requested, the value in menu 1.5 must be 0.
42
All manuals and user guides at all-guides.com
1.5 dEL1 - Setting of relay 1 switching on/off time delay.
2.0 rE 2 - SETTING OF PARAMETERS FOR RELAY 2.
3.0 dISP - SCALING OF DISPLAY.
3.1 d-LO - Setting of 0% display.
3.2 d-HI - Setting of 100% display.
3.3 d-Pt - Setting of decimal point.
3.4 LEd - Test of LED segments.
4.0 APP - SELECTION OF APPLICATION.
4.1 EFS / dFS - Setting of access to a fast change of setpoint.
Normally Closed
4.2 PAS - Programming access code.
Possible selections are 0...99.99 s.
The time delay is the period in which the input value must be present
before the relay switches state.
If no time delay is requested, the value must be 0.
These are set the same way as the parameters for relay 1.
Possible selections are -9999...9999.
Possible selections are -9999...9999.
Possible selections are no decimal point, position 1, 2, or 3.
All segments and LEDs must light up and the relays will be activated.
If the password differs from 0040, the relays and relay LEDs will not
light up.
Possible selections are EFS or dFS.
Access to a fast change of setpoint is determined by the (EFS - Enable
Fast Setting) fast change of setpoint is possible, or (dFS - Disable Fast
Setting) blocking of a fast change of setpoint.
EFS has a higher priority than menu 4.2 (PAS).
Possible selections are 0...9999.
When the password is 0040, all menu items can be changed. When the
password is <> 0040, programming of all menu items is blocked, but
reading of settings is possible. If fast setting is enabled, the set points
can be changed by fast setting.
43