LED alarm relay indications
LED alarm relay operation table
Start up sequence
Pump status
Not powered
Powered
Powered
❋ Alarm relay operation is user configurable see page 9 ❋
LED indications in operation
No power
Start up LED sequence
(default mode)
Start up LED sequence
(peripheral mode)
Standby mode –
waiting for water
Pumping water
High water level mode
Alarm mode –
relay activated
Reconfigure code
Condensate level
N/A
Below alarm level
Alarm-activated
(normally closed)
Default operation
NC
COM
NC
COM
NC
COM
NC
COM
NC
COM
NC
COM
NC
COM
NC
COM
NC
COM
Pump is miswired or no incoming voltage. Problem
with A/C system or alarm is miswired.
Alternating red/ green flashes 5x only then stops
and goes to standby mode.
Alternating red/ green flashes 5x only then stops
and goes to standby mode.
Blinking green continuously.
Solid green. Running in low, med low, med high, or
high power config. normal operation.
Blinking red. Running above high water level.
Solid red. Pump cannot keep up with water input.
To prevent water overflow break power to A/C until
water level reduces.
Pump has had 3 extra long run cycles, reconfigure
dip- switches for more capacity.
English
(normally open)
Peripheral Mode
NC
COM
NC
COM
NC
COM
NC
COM
NC
COM
NC
COM
NC
COM
NC
COM
NC
COM