Use with factory setting
Mounting of the adapter
Step 1
Screw the sensor into the
adapter.
Step 2
Clamp sensor and adapter into a
clamping device (C). The sealing
chamfers (D) must not be dam-
aged. Tighten the sensor with a
spanner.
Tightening torque: 20 Nm.
Electrical connection
The unit must be connected by a suitably qualified electrician.
The national and international regulations for the installation of
electrical equipment must be observed.
Voltage supply to EN50178, SELV, PELV.
Disconnect power before connecting the unit as follows:
2 wire connection
1
BN
2
WH
4
BK
3
BU
Core colours of ifm sockets:
1 = BN (brown), 2 = WH (white),3 = BU (blue), 4 = BK (black);
n.c. = not connected.
3 wire connection
L +
L-
n.c.
n.c.
1
BN
L +
2
WH
4
BK
n.c.
3
BU
L-
41
C
D
Connector view
(sensor)
1
4
2
3
15
2