C H A P I T R E 6
S
PÉCIFICATIONS
Input
Input Frequency 60Hz, +/- 3%, 50Hz Available upon request
Synchronizing Slew Rate 1Hz per second nominal
Protection Input Circuit Breaker
Voltage Harmonic Distortion < 10% (For Resistive Load)
Power Factor .5 lag/lead
Output
Static Voltage Load current change +/-4%, battery discharge +/-12.5%
Dynamic Voltage +/- 3% for +/-25% load step change, +/-6% for a 50% load step change
Harmonic Distortion < 3% THD for linear load
Output Frequency 60Hz +/- .05Hz during emergency mode
Load Power Factor .5 lag to .5 lead
Inverter Overload 115% for 10 minutes; 150% for 16 line cycles
Protection Optional Output Circuit Breaker
Battery
Protection Automatic low-battery disconnect; automatic restart upon utility return.
Disconnect Circuit Breaker
Environmental
Altitude < 3000m (10,000 feet) above sea level without derating
Operating Temperature Inverter: 0°C to 40°C (32°F to 104°F)
Storage Temperature -20 to 70 degrees Celsius (electronics only)
Relative Humidity < 95% (non-condensing)
General
Generator Input Compatible with generators (10x unit size or larger)
Control Panel Microcontroller 4 x 20-character OLED display with touch pad controls/functions & scrolling system status.
Metering Input & Output Voltage, Battery Voltage, Battery & Output Current, Output VA, Temperature, Inverter Wattage
Communications RS-232 port (DB9)
Manual Maintenance Bypass Optional internal, or optional external without internal distribution breakers.
Alarm Contacts Optional Summary Form "C" Contacts
Warranty 1 year standard warranty includes all parts, labor, & travel expenses within 48 contiguous states. Up to 10 years
Factory Start-up Purchase factory start-up & receive 1 additional year of warranty.
5 Year Service Plan Purchase 5 year service plan & receive free factory start-up.
Physical
Cable Entry Top or Side
13
General Specifications
Voltage 120 or 277 or 347Vac 1-phase 2-wire +10% -20%. Contact factory for all other voltages.
Voltage 120 or 277 or 347Vac 1-phase 2-wire. Contact factory for all other voltages.
Type Valve-regulated sealed lead-calcium. Contact factory for additional battery types.
Charger Microcontroller two stage charger (recharge - 24HR)
Battery: 20°C to 30°C (68°F to 86°F)
Design Stand-By UPS, PWM inverter type utilizing IGBT technology with 2mS transfer time.
Alarms High/Low Battery Charger Fault, Near Low Battery, Low Battery, Load Reduction Fault, Output Overload
High/Low AC Input Volts, High Ambient Temperature, Inverter Fault, Output Fault, Optional Circuit Breaker Trip
prorated warranty on batteries. Extended warranties, preventative maintenance and customized service plans
are available.
Cabinet Freestanding NEMA Type 1
Cooling Forced Air, during emergency mode.
Access Front
116322A – Manuel d'utilisation du système