Télécharger Imprimer la page

Mitsubishi Electric MXZ-3B24NA Notice D'installation page 8

Masquer les pouces Voir aussi pour MXZ-3B24NA:

Publicité

Les langues disponibles

Les langues disponibles

5.
RELOCATION AND MAINTENANCE
5-1. PUMPING
DOWN
When
relocating or disposing of the air conditioner, pump down the system following the procedure below so that refrigerant is not released into the atmosphere.
1) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
2) Fully close the stop valve on the liquid pipe side of the outdoor unit.
3) Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa [Gauge]
(0 Ibffin.? [0 kgf/cm').
4) Start the emergency COOL
operation on all the indoor units.
To start the emergency operation in COOL
mode, disconnect the power supply plug and/or turn off the breaker. After 15 seconds, connect the power supply plug
and/or turn on the breaker, and then press the E.O. SW once. (The emergency COOL
operation can be performed continuously for up to 30 minutes.)
5) Fully close the stop valve on the gas pipe side of the outdoor unit when the pressure gauge shows 0.05 to 0 MPa [Gauge] (approx. 7.25 to 0 Ibffin' [0.5 to 0 kgf/cm').
6) Stop the emergency COOL operation.
To stop operation, press the E.O. SW several times until all LED lamps turn off. Refer to operating instructions for details.
A WARNING
When
pumping
down
the
refrigerant,
stop the compressor
before
disconnecting
the refrigerant pipes. The compressor may burst if air etc. get into it.
En-7

Publicité

loading

Ce manuel est également adapté pour:

Mxz-3b30naMxz-4b36na