2. OUTDOOR UNIT INSTALLATION
2-1. INSTALLING THE UNIT
*
Be sure to fix the unit's legs with bolts when installing it.
*
Be sure to install the unit firmly to ensure that it does not fall by an earthquake or a gust.
°
Refer to the figure in the right for concrete foundation.
*
Do not use the drain socket and the drain caps in the cold region. Drain may freeze and it makes the fan stop.
Anchor leg
500
Fix here with
g
(19-11/16)
M10 bolts.
2
°
yy
ao.
Left ____
@
l
5
V
_
A
Anchor both length
Anchor both pitch
We Sees? ZZ
Z
7
(atm fe
Make with wider.
2-2. CONNECTING
WIRES FOR OUTDOOR
UNIT
*
Be sure to use special circuits for room air conditioner.
ELECTRICAL SPECIFICATIONS
° Wiring work should be based on applicable technical
standards.
OUTDOOR UNIT
MXZ_3B24NA
MXZ_3B30NA
MXZ_AB36NA
| Bing connections should b e mage folowing he daaram
Poa soy PHASE,
OT, 80
Max. Fuse size (time delay) (A)
20
25
Min. Circuit Ampacity (A)
18
23
Fan motor (F.L.A)
0.93
0.93
(R.L.A)
11
14.4
Compressor
(L.R.A)
15
15
Control voltage
Indoor unit-Remote controller : (Wireless)
Indoor unit-Outdoor unit : DC12-24V
1) Remove the service panel.
2) Remove the conduit cover.
3) Attach
the conduit connector to conduit cover with lock nut then se-
cure it to the unit with screws.
Connector
4) Connect ground wires to the TB support.
5) Loosen
terminal
screw,
and
connect
indoor/outdoor
unit connecting
wire (B) from the indoor unit correctly on the terminal block. Be careful
oS
not to make
mis-wiring.
Fix the wire to the terminal block securely so
that no part of its core is appeared, and no external force is conveyed
to the connecting section of the terminal block.
6) Firmly tighten the terminal
screws
to prevent them
from
loosening.
After tightening, pull the wires lightly to confirm that they do not move.
7) Perform 5) and 6) for each indoor unit.
8) Connect power supply cord (A).
9) Close
the service
panel
securely.
Make
sure that 3-2.
PIPE
CON-
NECTION
is completed.
¢ After making
connections between
both power supply cord (A) and
indoor/outdoor
unit connecting
wire (B), be sure to fix both cable
CITT.
p~ Terminal block
uf
for power supply
and wire with cable clamps.
Ww
Screws
x
,
Service panel
4BS6NA
Connecting order
Power supply
*
Connect
the terminal
block
in
following order.
re
A>B>CD—P
(oli El
D unit is for 4B36NA only
rey
i
i
t
;
|
=e
Terminal block for
indoor/outdoor unit
Remark:
*
A disconnect switch should be required. Check the local code.
* Use a ring tongue terminal in order to connect a ground wire to terminal.
*«
Connect wires to the matching numbers
of terminals.
sam
¢«
Be sure to attach
each
screw
to its correspondent
terminal
INDOOR UNIT
ALI
35 mm
(5/8 in.)
when securing the cord and/or the wire to the terminal block.
.
1-3/8
i n .
K
q
(
™)
CONNECTING WIRES AND CONNECTING GROUND WIRE
~
a
*
Use solid conductor AWG14 or stranded conductor AWG14.
Groundin
*
Use double insulated copper wire with 600 V insulation.
re ql x
terminal 2
a
¢
Use copper conductors only.
i
1
Lead wire
*
Follow local electrical code.
208/230 VAC
Power supply
1 phase 60 Hz
Disconnect
208/230 VAC
POWER SUPPLY CABLE AND GROUND WIRE
switch *
1 phase 2 wires 60 Hz
.
+ Use solid or stranded conductor AWG14 (MXZ-3B//AWG12 (MXZ-
|
|_|
pre
Grounding
4B)
;
terminal ™
pounding
eh
ermine
* Use copper conductors only.
ermine
LGA. PM
*
Follow local electrical code.
Oo"
O
bs
Sis2sg
Sisas
=
Z\ WARNING:
Terminal block
ALO
Terminal block
Terminal block 4
Ground
Use the indoor/outdoor unit connecting wire that meets the Stand-
ards to connect the indoor and outdoor units and fix the wire to
OUTDOOR UNIT
the terminal
block securely so that no external force is conveyed
D unit is for 4836NA only
to the connecting
section
of the terminal
block. An
incomplete
connection or fixing of the wire could result in a
fire.
For future servicing, give extra length to the connecting wires.
En-4