STANDARDS – EN 60670-1; EN 60670-24
SECTION 7 CLASSIFICATION
7.1
Nature of the material
7.2
Type of installation
7.3
Types of inlets (outlets)
7.4
Means for fixing cables and pipesx
Minimum and maximum temperatures during
7.5
the installation
Boxes or enclosures for hollow or partitions,
7.7
classified according to 7.2.1.3
7.8
Means for fixing the devices to the boxes
7.102
Enclosure
Resistance of the recessed housing part enclosure embedded area (back case box) to the glow wire test at 850°
IK Test - IK07
The maximum permissible load inside the enclosure 2x4 is 1,4 kg
(The maximum load was verified by the maximum weight of the MCB applied and with an increase of 1,5)
The maximum permissible load inside the enclosure 3x4 is 2,1 kg
(The maximum load was verified by the maximum weight of the MCB applied and with an increase of 1,5)
The maximum permissible load inside the enclosure 4x4 is 2,8 kg
(The maximum load was verified by the maximum weight of the MCB applied and with an increase of 1,5)
Rated Voltage - 250 V ~ | Rated Current - 63 A
INFORMATIONS
ANNEX BB
BB3
Devices to be Integrated by the Installer
BB5
Connections
BB6
Protection Against Electric Shock
BB8
Wiring
STANDARD - EN 50085-1
SECTION 9
9.4
Mechanical connections by screws
STANDARDS - IEC 60884-1; NP 1260-1
SECTION 9 CLASSIFICATION
9.4
Fixing of low voltage devices
EFAPEL reserves the right to modify this document or the products contained in it without notice. If in doubt please contact EFAPEL.
WORKSTATIONS FLUSH MOUNTING
Insulating
Embedded, semi-embedded or integrated into: walls, ceilings
or furniture, non-combustible; walls, ceilings or furniture,
combustible.
With inlets for plain or corrugated pipes
With cable retention
-5 °C to +60 °C
Degree of protection of the enclosure: IP3XC
Boxes designed to allow other means of fixing
PD Enclosure (for predetermined equipment)
The devices integrated in the enclosure by the installer shall
comply with their applicable product standards, (e.g. 1 MCB shall
comply with IEC 60898-1, 1 RCCB shall comply with IEC 61008-
1 and 1 RCBO shall comply with IEC 61009-1). The sockets shall
comply with IEC 60884-1 and have safety shutters (Ref. 45132 S,
45112 S). Compatible with devices 45x45 - MEC Q45.
Terminals must be used in accordance with the standards
EN 60998-2-1.
Active parts shall remain not accessible after devices are installed
in the enclosure. Devices mounted in the enclosure shall have a
minimum IP degree of IP3X.
The installation must ensure that the internal wiring shall be
such that minimum creepage distances between live parts and
metallic accessible or non-accessible parts are not lower than
3mm. The cross-sections of conductors shall be in accordance
with the wiring rules.
0,8 Nm
WORKSTATIONS FLUSH MOUNTING
90 N x 1,5=135 N
EN