6. Troubleshooting
Condition
One UPS displays:
Load unbalance
Firmware download is
not possible
7. Specifications
Input Bypass
Output
Overall dimensions D x W x H (inch / mm)
Weight (lb / kg)
Performance
Nominal voltage
Frequency
Input nominal current
Maximal power
Standards
Safety
EMC
Performance
ESD
Radiated field
EFT
Fast transients
Electromagnetic field
Conducted
magnetic field
Marking
Environment
Operating
temperature
Storage temperature
Transit temperature
Humidity
Operation Altitude
Transit Altitude
Page 24
Possible cause
One of the "UPS output" switches is off
on the back of the ModularEasy
One of the two UPS is in Online or
Battery mode
9PXMEZ6Ki
N/A
4 IEC 16A + Terminal blocks
27 x 17 x 5 / 690 x 440 x 130
22.8 / 10.3
200 - 240 V ~
50/60 Hz
60A
12000 VA
IEC/EN 62040-1 / Ed.1: 2008
IEC/EN 62040-2 / Ed.2: 2006
IEC/EN 62040-3 / Ed.2.0: 2011
IEC 61000-4-2 : level 3.
IEC 61000-4-3 : level 3.
IEC 61000-4-4 : level 4.
IEC 61000-4-5 : level 4.
IEC 61000-4-6 : level 3.
IEC 61000-4-8 : level 4.
CE
0 to 40°C (32 to 104°F)
-15 to 60°C (5 to 140°F)
-25 to 55°C (-13 to 130°F)
0 to 95% no condensing
Up to 3,000 meters (9,843 ft) above sea level with 10% derating per 1000m
Up to 10,000 meters (32,808 ft) above sea level
Action
Switch on the "UPS output" switch on
the ModularEasy
Select Standby or Bypass mode
9PXMEZ11Ki
Terminal blocks
4 IEC 16A + Terminal blocks
32.6 / 15
200 - 250 V ~
100A
22000 VA
614-09354-01_EN