Voltwerk VS 3, 4, 5
(–) (1)
(+) (1)
5.3:
Wires with connector plug and socket
(1)
Stripped, non-crimped cable
Ferrule
(2)
Connector plug
(3)
Connector socket
(4)
Crimping the cable
1. Strip the cable to 25 mm.
The connector plugs and sockets are MCIV compatible.
Material damage due to damaged wire strands
Damaged wire strands may break and heat up.
| Do not damage the wire strands.
2. Strip wires to 14 mm.
Risk of damage from incorrect crimping die!
| Only use crimping die D made by Wieland (Article number
05. 502. 2300. 0).
Operating manual
5 Installation
(2)
(2)
(–) (3)
(+) (4)