5
Routine maintenance
Periodic and correct maintenance of the vacuum pump will ensure a long operation life and con-
stant performance.
Lubrication
The oil provided with the pump has been specially formulated & manufactured to lubricate vacu-
um pumps; it is special as it features minimum viscosity fluctuation when in use under a wide
temperature range.
The type of lubricant supplied with the pump allows the evacuation of systems operating refrig-
erants. Only working with ROTHENBERGER POE synthetic oil.
The required amount of lubricating oil depends on the size of the pump container specified in the
section "Technical data" and must correspond to the quantity required until the dimensions of
the sight glass are reached.
Replace the oil charge no later than 20 hours of operation.
Oil could be polluted by other oil, humidity, refrigerants, etc. It is mandatory to use oil in perfect
conditions to assure a perfect performance of the pump.
Oil-change
Over-used lubrication oil damages the pumps' mechanism; make sure to replace oil as soon as
it starts to turn cloudy. For conducting the oil-change, the pump must be switched off. For
changing the oil proceed as follows:
Unscrew the oil drainage plug located on the lower part of the pump
Check that oil comes out completely from the pump
Tightly screw the oil drainage plug back on
Re-fill the pump with oil (see "Filling of oil")
WARNING: Do not pollute the environment by spilling oil; the lubricant oil is a special
waste and must be disposed of according to relevant local law / guidelines in force.
6
Extraordinary maintenance / repair
Conduct extraordinary maintenance or repair whenever serious faults occur such as overheat-
ing, poor ultimate vacuum, persistent loudness / noise, blocked pump or any other irregular func-
tioning.
In that case, the pump needs to be disassembled, parts need to be cleaned, repaired or re-
placed. Only qualified service staff shall carry out such maintenance or repair work; otherwise
the warranty will be void.
For any information please contact our Service-After-Sales.
7
Troubleshooting
Problem
The pump doesn't
work
Overheating
16
All manuals and user guides at all-guides.com
Solution
Check that the pump is connected to the power supply.
Check that the plug and cable are not damaged.
Check that the power supply is suitable for the pump requirements (see
the label of the pump).
Check that the pump is filled up with oil-
Contact our Service-After-Sales.
Check that the pump is filled up with oil.
Check that the pump is not covered and that air could flow easily.
Check that the power supply is suitable for the pump requirements (see
the label of the pump).
Contact our Service-After-Sales.