Drain Connection (AIR125R and AIR125F Only)
Installation Notes
The AIR125 HRV's have a 4-position drain spout to allow for easy and quick installation of the
condensate drain hose (see below).
The AIR125 HRV's may produce some condensation during a defrost cycle. This water should flow
into a nearby drain, or be taken away by a condensate pump.
1. Position drain spout towards desired drainage direction and fasten to HRV cabinet with 4 sheet
metal screws provided.
2. Seal drain spout to bottom of HRV cabinet with silicone.
3. Cut one length of 1/2 in drain hose (not included) and connect to the drain spout.
To Drain
Drain
Spout
Drain Pan Inside Door
Note
AIR125 HRV is to be mounted with door and drain down
Caution
The HRV and all condensate lines must be installed in a space where the temperature is maintained above the freezing
point or freeze protection must be provided.
Drain trap and tubing must be below bottom of door with 1/4 in per foot downwards slope away from unit.
A secondary drain pan may be required to protect from condensate leakage.
Drain Hose Plumbing
1/2 in I.D.
Drain Hose
The AIR125 HRV 4-Position Drain
360˚
8