BURNER FLAMES
Inspect the burner flames through the viewport and
compare them to the drawings in Figure 31. A properly
operating burner should produce a soft blue fl ame. Blue
tips with yellow inner cones are satisfactory. The tips of
the fl ame may have a slight yellow tint. The fl ame should
not be all yellow or have a sharp blue-orange colour.
Contaminated air may cause an orange coloured fl ame.
Contact a qualifi ed service technician if the fl ame is not
satisfactory
TIPS MAY HAVE
A YELLOW TINT
YELLOW INNER
CONES ARE
SATISFACTORY
CORRECT FLAME
SOFT BLUE
Figure 31
SERVICING THE WATER HEATER
Servicing this water heater shall be done by qualifi ed
service personnel only.
1. Before performing any maintenance, it is important
to turn "OFF" the gas supply to the water heater at
the manual gas shut-off valve. This valve is typically
located beside the water heater. Note the position of
the shut-off valve in the open/on position, then proceed
to turn it "OFF" (see Figure 1).
2. With the water heater shut-off, allow suffi cient time for
the it to cool off before performing any service.
REMOVING AND REPLACING THE GAS CONTROL
VALVE/THERMOSTAT
Removing The Gas Control Valve/Thermostat:
1. Turn the gas control/temperature knob to the "OFF"
position (see Figure 30 and Figure 32).
2. Turn "OFF" the gas at the manual gas shut-off valve
(see Figure 1).
3. Drain the water heater. Refer to the "Draining, Refi lling
And Flushing" section and follow the procedure.
4. Disconnect the igniter wire from the igniter lead wire.
Use needle nose pliers to disconnect the thermopile
connector. Disconnect the pilot tube (7/16" wrench)
and manifold tube (3/4" wrench) at the gas control
valve/thermostat (see Figure 32).
Note: Propane (LP) Gas systems use reverse (left-hand)
threads on the manifold tube.
5. Refer to "Gas Piping" and disconnect the ground joint
union in the gas piping (see Figure 13). Disconnect the
remaining pipe from the gas control valve/thermostat.
6. To remove the gas control valve/thermostat, thread
a 100mm (4") section of gas pipe into the inlet
and use it to turn the gas control valve/thermostat
(counterclockwise). Do not use a pipe wrench or
equivalent to grip body. Damage may result, causing
leaks. Do not insert any sharp objects into the inlet or
outlet connections. Damage to the gas control valve/
thermostat may result.
All manuals and user guides at all-guides.com
INCORRECT
FLAME LAZY
YELLOW
www. gsw-wh .com
Replacing The Gas Control Valve/Thermostat:
To replace the gas control valve/thermostat, reassemble
in reverse order. When replacing the gas control valve/
thermostat, thread a 100mm (4") section of gas pipe into
the inlet and use it to turn the gas control valve/thermostat
(clockwise). DO NOT OVER TIGHTEN; damage may
result.
•
Be sure to use approved Tefl on
compound on the gas piping connections and fi tting
on the back of the gas control valve that screws into
the tank.
•
Be sure to remove the pilot ferrule nut from the new gas
control valve/thermostat. Reconnect the manifold tube,
pilot tube, igniter wire and the thermopile connections.
•
Turn the main gas supply "ON" and check the gas
supply connections for leaks. Correct any leak found.
•
Light the pilot and main burner, then check the manifold
tube and pilot tube connections for leaks. Use an
approved noncorrosive leak detection solution. If such
a solution is not available, use a mixture of hand dish
washing soap and water (one part soap to 15 parts
water) or childrens' soap bubble solution. Bubbles
forming indicate a leak. Correct any leak found.
•
Be sure tank is completely fi lled with water before
lighting and activating the water heater. Follow the
lighting instructions on the label or see "Lighting
Instructions" to restart the water heater.
If additional information is required, reference the number
on the cover of this manual for service information.
TEFLON
®
is a registered trademark of E.I. Du Pont De Nemours and
Company
REMOVING THE MANIFOLD/BURNER ASSEMBLY
1. Turn the gas control/temperature knob to the "OFF"
position (see Figure 30 and Figure 32).
2. Turn "OFF" the gas at the manual gas shut-off valve
(see Figure 1).
GAS CONTROL/
TEMPERATURE
KNOB
IGNITER
BUTTON
IGNITER
LEAD
WIRE
PILOT
IGNITER
TUBE
WIRE
Figure 32
3. Remove the outer door.
4. Disconnect the following from the gas control valve/
thermostat: pilot tube (7/16" wrench), igniter wire (from
the igniter lead wire), and manifold tube (3/4" wrench)
(see Figure 32).
Note: Propane (LP) Gas systems use reverse (left-hand)
threads on the manifold tube.
5. Use needle nose pliers to disconnect the thermopile
connector from the gas control valve/thermostat (see
Figure 32).
®
tape or pipe joint
THERMOPILE
CONNECTOR
WHITE
WIRE
RED WIRE
MANIFOLD TUBE