Operation of the room unit
The temperature is adjusted with rotary switch A. The figure on the display will flash five
times and then become set.
ECO button
The ECO function is activated by pressing the ECO button once
(default setting: 8 h /20.5 ºC). When the function is engaged, the
number of hours is shown in the upper right-hand corner for 20
seconds.
When the ECO button is pressed for more than 3 seconds, the AWAY
function is activated (default setting: 30 days / 18.5 ºC). The duration of
the function in days is shown in the upper right-hand corner.
User menu
To access the menu, press button C for more than 3 seconds. Move in the menus with
rotary switch A and activate the selected function with button C. The variable to be
changed flashes (page 2, Figure 1).
Minimum temperature for supply water
Radiator heating: min. 5–35 ºC / factory setting: min. 5 ºC
Floor heating: min. 5–35 ºC / factory setting: min. 20 ºC
Maximum temperature for supply water
Radiator heating: max. 40–95 ºC / factory setting: max. 60 ºC
Floor heating: max. 20–40 ºC / factory setting: max. 35 ºC
Time: hh, mm
Weekday number 1–7
1 = Monday, 5 = Friday, 7 = Sunday
The temperature for the ECO function is xx.y ºC and the duration is x h.
The factory setting is 20.5 ºC / 8 h.
The temperature for the AWAY function is xx.y ºC and the duration
in days is 1–30–infinite (= for now).
The factory setting is 18.5 ºC / 30 days.