13 Interface IO-Link
Index
Subin-dex
hex
hex
0x3C
0x01
SetPoint 1 = SP1
0x3C
0x02
SetPoint 2 = rP1
0x3E
0x01
SetPoint 1 = SP2
0x3E
0x02
SetPoint 2 = rP2
0x57
0x00
Operating hours
0x60
0x00
Password
0xD0
0x00
Delay Switching Time 1 R / W
0xD1
0x00
Delay Back Switching
Time 1
0xD2
0x00
Delay Switching Time 2 R / W
0xD3
0x00
Delay Back Switching
Time 2
0xD5
0x00
Min Pressure Value
0xD6
0x00
Max Pressure Value
0xD7
0x00
Damping
0x0010
0
Get Vendor Name
0x0011
0
Get Vendor Text
0x0012
0
Get Product Name
0x0013
0
Get Product ID
0x0014
0
Get Product Text
0x0015
0
Get Serial Number
0x0016
0
Get Hardware Revision R
0x0017
0
Get Software Revision R
13.8 Réglage du décalage et de la valeur finale
Plage de mesure
0 à 10 bars
-1 à 50 bars
0 à 400 bars
GEMÜ 3140
Object name
Access
R / W
R / W
R / W
R / W
R
W
R / W
R / W
R
R
R / W
R
R
R
R
R
R
Décalage ± 5%
min.
-0,5 bars
-1 bars
-1 bars
Length
Value Range
2 octets
Process Data
2 octets
Process Data
2 octets
Process Data
2 octets
Process Data
4 octets
0 ... 4294967295
2 octets
0000 ... 9999
2 octets
0..500
2 octets
0..500
2 octets
0..500
2 octets
0..500
2 octets
Process Data
2 octets
Process Data
2 octets
0...1000
in 10 ms steps
64 octets
Process Data
64 octets
Process Data
64 octets
Process Data
64 octets
Process Data
64 octets
Process Data
64 octets
Process Data
64 octets
Process Data
64 octets
Process Data
max.
+0,5 bars
+1,55 bars
+20 bars
20 / 24
Gradient
1
0.1
0.1
0.1
0.1
1
Valeur finale 90% - 100%
min.
9 bars
44,9 bars
360 bars
Unit
Default
75%
74%
85%
84%
h
0
0
sec
0
sec
0
sec
0
sec
0
ms
0
max.
10 bars
50 bars
400 bars
www.gemu-group.com