LISTE DE VÉRIFICATION AVANT DÉMARRAGE
1. q ENLEVER LE MATÉRIEL D'EMBALLAGE DU CÔTÉ GAUCHE DE LA SOUFFLERIE.
2. q ENLEVER LE MATÉRIEL D'EMBALLAGE SOUS LA POMPE À EAU.
3. q ÉVACUER L'AIR PRÉSENT DANS LES CONDUITES D'EAU.
4. q ÉVACUER L'AIR PRÉSENT AU BOUT DE LA POMPE À EAU, PAR LA VIS DE
PURGE. OUVRIR DOUCEMENT LA VIS DE PURGE D'UN DEMI-TOUR, JUSQU'À
CE QUE L'AIR S'ÉCHAPPE. ATTENTION À CE QUE L'EAU NE COULE PAS SUR
LE PANNEAU DE COMMANDE, DANS LE COMPARTIMENT DE LA SOUFFLERIE.
5. q INSTALLER LE CAPTEUR D'AIR DISTRIBUÉ EN AVAL DU SERPENTIN
CLIMATISANT, SI CE DERNIER SE TROUVE DANS LE CONDUIT D'AIR DIS-
TRIBUÉ, EN AVAL DU TRAITEUR D'AIR. CONSULTER LES CONSIGNES
D'INSTALLATION.
6. q INSTALLER LE CAPTEUR OPTIONNEL D'AIR REPRIS EN AMONT DU SER-
PENTIN CLIMATISANT, SI CE DERNIER SE TROUVE DANS LE CONDUIT D'AIR
REPRIS, EN AMONT DU TRAITEUR D'AIR.
7. q SI LE SERPENTIN CLIMATISANT SE TROUVE DANS LE CONDUIT D'AIR
REPRIS, EN AMONT DU TRAITEUR D'AIR, INSTALLER LE FILTRE À AIR EN
AMONT DU SERPENTIN CLIMATISANT.
8. q CONFIRMER QUE LA SOURCE D'EAU CHAUDE FOURNIT UNE EAU DONT
LA TEMPÉRATURE EST SUPÉRIEURE À LA TEMPÉRATURE MINIMALE SÉLEC-
TIONNÉE. POUR LES RÉGLAGES DES COMMUTATEURS DIP, CONSULTEZ LE
GUIDE.
9. q LANCER L'APPEL DE CHAUFFAGE.
q LA POMPE SE MET EN MARCHE.
q LA SOUFFLERIE SE MET EN MARCHE.
10. q ANNULER L'APPEL DE CHAUFFAGE.
LA POMPE S'ARRÊTE.
ENVIRON 1 MINUTE PLUS TARD, LA SOUFFLERIE S'ARRÊTE.
11. q COUPER L'ALIMENTATION AU CONDENSATEUR EXTERNE.
LANCER L'APPEL DE CLIMATISATION.
LORSQUE LA SOUFFLERIE DU GÉNÉRATEUR DE CHALEUR EST EN MARCHE,
CONFIRMER LA PRÉSENCE D'UN COURANT 24 V À Y ET À C AU RELAIS SUR
LE PANNEAU DE COMMANDE.
SI LE TEST RÉUSSIT, RÉTABLIR L'ALIMENTATION.
12. q ANNULER L'APPEL DE CLIMATISATION.
ENVIRON 1 MINUTE PLUS TARD, LA SOUFFLERIE S'ARRÊTE.
41