Connect the batteries to the
power supply terminals (3)
using the correct wire complete
with protection with fuse.
Be careful with the battery
polarity during the
connection.
This ensures that the system complies with level 1 of CEI 79-2 standard.
In order to comply with level 2, install the power supply and the battery on a distribution board flush mounted to the wall, using items
F496/FF and F496/PF.
When fitted inside the F115/8A enclosure, the device must be kept away from water drips and sprays.
The following table gives the maximum absorption which the system must have depending on the battery installed
and the life-time level required.
In all cases the maximum absorption must not exceed 700 mA.
lifetime when
there is
a power cut
(*) In these cases the system respects level 2 of standard IEC 79-2.
The 24 Am battery is not cover by IMQ Alarm certification
All manuals and user guides at all-guides.com
Install the container
closing covers
24 h
15 h
8 h
If you want to protect the battery
compartment, connect the contact on the
container item F115/8B (4) to a tamper line.
type of battery installed
7,2 Ah
12 Ah
110 mA (*)
190 mA (*)
180 mA
300 mA
340 mA
560 mA
4
24 Ah
380 mA
600 mA
700 mA