Setting Up the Transducer
1.
Turn the transducer power supply on. The instrument will go through a
preprogrammed power-up sequence. The internal display will sequence
through the current settings: Calibration date "CALdAtE", "=", month and
year "03.2013"(March 2013), measurement units "mEtErS"(m/s) or
"FEET"(ft/min), "=", selected output type and range "0-5V" and the time
constant "tc = 1.00" in seconds. The display will then show velocity
readings.
2.
Push the SET button to enter setup mode. When setup mode is entered,
the transducer voltage/current output will drop below zero.
3.
Use the
4.
Use the SET button to advance to the next setup message.
NOTE: The output signal is disabled during the 15 second warm-up period
Setup Message
SELECt UnitS
SELECt FULL
SCALE
SELECt OUtPUt
SELECt tc
AdJUSt ZErO
AdJUSt SPAn
1.800.561.8187
and
buttons to select the desired setting.
and when the transducer is in setup mode.
FEEt (ft/min) or mEtErS (m/s)
Select full scale of the velocity range
Select Output Type: 0-5V, 0-10V, 1-5V, 2-10V, 4-20mA,
0-20mA
Select Time Constant: 0.05 to 10 seconds (see page
12)
Adjusts voltage/current output signal at zero velocity
(see page 14)
Adjusts the voltage/current output by ±15% (see
page 13)