BOOSTER_A
AL04
input over-
voltage.
BOOSTER_A
AL05
input under-
voltage.
BOOSTER_B
AL06
input over-
voltage.
BOOSTER_B
AL07
input under-
voltage.
AL08
Anti-islanding.
Phase of utility
AL 13
fails.
Waveform of
AL14
utility fails.
Inverter voltage
AL09
unbalance.
AL10
GFDI.
AL11
Isolation fault.
INFOSEC UPS SYSTEM - 4, rue de la Rigotière - 44700 Orvault - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)2 40 94 29 51 - hotline@infosec.fr – 04 10 AA 68 203 18
All manuals and user guides at all-guides.com
Over or under voltage
at DC input.
No utility or utility
fails.
Inverter voltage
waveform is in
unbalance.
Leakage current on
ground conductor is
too high.
The impedance is
between PV (+) & PV
(-) and ground is
smaller than 1MΩ.
1. Disconnect ALL PV (+) or PV
(-).
2. Check the open PV voltage is
outside the 120Vdc ~ 500Vdc.
3. If PV voltage is normal and
the problem still occurs, contact
your local distributor for help.
1. Disconnect ALL PV (+) or PV
(-).
2. Check grid connection, such
as wires and connectors.
3. Check grid usability.
4. If Utility is normal and the
error code keeps recurring,
contact your local distributor for
help.
1. Shut down inverter (Unplug
PV generator from the input).
2. Check grid usability and
Restart inverter (plug PV
generator from the input).
3. If error code keeps
recurring, contact your local
distributor for help.
1. Unplug PV generator from
the input, check AC peripheral
system
2. After the problem is cleared,
re-plug the PV. Check the PV-
Inverter status.
3. If error code keeps
recurring, contact your local
distributor for help.
1. Disconnect ALL PV (+) or PV
(-).
2. Check the impedance
between PV (+) & PV (-) and
Ground. The impedance must
be larger than 2MΩ.
3. If error code keeps
recurring, contact your local
distributor for help.
29