Input:
Supply.voltage.universal............................... 21.6...253.VAC
.
.
Internal.consumption.................................... ≤.2.W.(2.channels)
Max..consumption........................................ ≤.4.W.(2.channels)
Outputs:
Output.voltage. . ............................................. >.18.VDC.at.20.mA
Output.current.per.channel.(max.)................ 28.mA
Relay outputs:
ON.within.limit............................................... >.3.8...<.20.5.mA
Vmax.............................................................. 2 50.VRMS
Imax. . .............................................................. 2 .ARMS
Max..AC.output.............................................. 1 00.VA
Max..load.at.24.VDC. . ................................... 1.A
EEx / I.S. approval:
DEMKO.99ATEX126256................................ ..
.
Applicable.for.zone....................................... 0,.1,.2,.20,.21.or.22
Ex / I.S. data:
U
................................................................. :.250.V
m
U
.................................................................. :.28.VDC
o
I
.. . ................................................................. :.93.mADC
o
P
.................................................................. :.0.65.W
o
L
. . ................................................................. :.3.mH
o
C
.................................................................. :.0.08.µF
o
GOST R approval:
VNIIM.&.VNIIFTRI,.Cert..no........................... See.www.prelectronics.com
Observed authority requirements:
EMC.2004/108/EC........................................ EN.61326-1
LVD.2006/95/EC. . .......................................... EN.61010-1
PELV/SELV. . ................................................... IEC.364-4-41.and.EN.60742
ATEX.94/9/EC. . .............................................. EN.50014,.EN.50020.and
.
22
All manuals and user guides at all-guides.com
50...60.Hz
19.2...300.VDC
II.(1).GD
[EEx.ia].IIC.
Standard:
EN.50281-1-1
Connections:
Supply:
31
32
33
Safe area:
Loop alarm
11
12
13
Loop alarm
21
22
23
Outputs for Ex area:
DC voltage
41
42
43
Gnd.
V+
DC voltage
51
52
53
Gnd.
V+
23