Hysteresis:
The hysteresis keeps the switch-
ing state of the output stable if
the system pressure varies about
the preset value. When the sys-
tem pressure is rising, the output
switches when the switch-on
point has been reached (SP1);
when the system pressure is
falling again, the output switches
back when the switch-off point
(rP1) has been reached.
The hysteresis can be set: First the switch-on point is set, then the
switch-off point with the requested difference.
Window function:
The window function enables
the monitoring of a defined
acceptable range. When the sys-
tem pressure varies between the
switch-on point (SP1) and the
switch-off point (rP1), the output
is switched (window function /
NO) or not switched (window
function / NC).
The width of the window can be
set by means of the difference
between SP1 and rP1. SP1 = upper value, rP1 = lower value.
16
P
SP
rP
1
0
1
0
acceptable range
P
SP
rP
1
0
1
0
hysteresis
t
Hno
Hnc
t