UL/ CSA Maximum short-circuit current ratings Coordination Type 2 - MS116 with AF contactors
Type
MS116-0.16
MS116-0.25
MS116-0.4
MS116-0.63
MS116-1
MS116-1.6
MS116-2.5
MS116-4
MS116-6.3
MS116-10
MS116-12
MS116-16
MS116-20
MS116-25
MS116-32
MS116
Minimum contactor size
480Y/277V
[kA]
AF09...AF16
30
AF09...AF16
30
AF09...AF16
30
AF09...AF16
30
AF09...AF16
30
AF26...AF38
30
AF26...AF38
30
AF26...AF38
18
AF26...AF38
18
AF26...AF38
18
AF26...AF38
18
AF26...AF38
18
AF26...AF38
18
AF30...AF38
18
AF38
18
Minimum contactor size
AF09...AF16
AF09...AF16
AF09...AF16
AF09...AF16
AF09...AF16
AF09...AF16
AF16
AF16
AF26...AF38
AF30...AF38
AF30...AF38
AF40
AF40
AF40
AF40
7
600Y/347V
[kA]
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
2CDC131011M6802 (j) / 12.2022