OPERATING INCIDENTS
The central unit does not stop
1. Stop the central
unit by pressing the
OFF button
YES
2. - Disconnect the central unit from the
network
- Start the central unit by pressing the
ON button
- Block the vacuum inlet manually
(as in the diagram opposite)
The central unit does
not stop
The central
unit stops
Localised leaks in the ductwork
or on the accessories
3. - Connect the hose to the central
unit, which is disconnected from
the network
- Use the STOP button on the
handle to stop the central unit
The central
unit stops
11/06/10
15:56
NO
- Have you had a thunderstorm recently?
- Electrically disconnect then reconnect your
central unit, then try again
- If the problem persists, contact your Aldes
After-Sales Service
There are leaks in the central unit
- Check that the central unit's cover is correctly
closed
- Check that the tank is positioned correctly
- If the problem persists, contact the Aldes
After-Sales Service
The central
unit does not stop
There are leaks in the accessories
- Check that the handle functions correctly
- Check that the hose has not been pierced
14
Page 14
There are leaks in the vacuum cleaning network
- Check that the ducts are airtight
- Check that the vacuum inlets are not open, distorted or pulled out from
the wall
Carry out a duct
network test,
with all vacuum
inlets closed.
C.Cleaner network test :
Keep pushing button OFF until the maintenance LED lights up in green.
Release button OFF, then press once button OFF then button ON, to make the test begin.
Green : pipework OK / Red = leak
FITTER'S ADJUSTMENTS
Adjusting the start-up sensitivity of the Central Unit (except C.DOOBLE):
Press and hold the OFF button until the maintenance LED lights up in green.
Release the OFF button, then press the ON button to make the maintenance LED flash
The number of flashes gives the current sensitivity setting on a 1 to 10 scale (the higher the
value the higher the sensitivity).
By default, the sensitivity is adjusted on 5.
Pressing the ON button increases sensitivity by one step.
Pressing the OFF button decreases sensitivity by one step.
In order to validate your choice, do not touch the buttons anymore and wait for 30 seconds,
letting the system record the new required parameters.
You now benefit from your new settings.
Synchronisation of the wireless handle with the C.POWER and C.DOOBLE units:
Keep pushing button OFF until the green LED light for servicing is ON.
Release button OFF then keep pushing the button on the handle until the 3 blue LED lights
on the C.Power unit are on.
The wireless handle is now synchronised with the receiver on the C.Power unit.
Carry out a duct network test:
15