LDX-L30 Series
FIG.6 - ENVIRONMENT ASSEMBLY STEPS
Attention! Do not stress mechanically the cables!
After connecting the wires on the batteries and after having placed the batteries in the enclosure, the LDX-L30 should appear as on the picture above.
FIG.7 - ENVIRONMENT BATTERY SETUP
Attention! Do not use Jumper 1 when Jumper 2 and 3 are connected.
FIG.8 - ENVIRONMENT
OPERATING TEMPERATURE
- 20°C to 40°C
According to battery limits indicated by the manufacturer
NOTES:
Data may change without prior notice in order to improve the product.
Please refer to the latest version of the Installation Instruction for each product by visiting
USE only Lead-acid Batteries 12 VDC 1.2 Ah.
Dimension 48.5 x 54.5 x 97.5 mm.
Faston type 4.8 mm
WR1: Red stranded wire 1.5 mm², length 140 mm.
WR2: Black stranded wire 1.5 mm², length 140 mm.
WR3: Black stranded wire 1.5 mm², length 120 mm.
WR4: Red stranded wire 1.5 mm², length 120 mm.
Attention!
WR1 and WR2 must be connected at the Battery 1.
WR3 and WR4 must be connected at the Battery 2.
The colored wires must respect the Battery polarity.
The colored wires should respect the bending as indicated in the diagram on side.
belfuse.com/power-solutions.