Basic Programming
Parameter
Default
Name
Value
SHIFT 1 SHIFT 2
On / Raise
Off / Lower
Walk test
Off
Timeout
1, 10, 20
(Time
20 mins
(1, 10, 20
adjustment)
minutes)
Lux on level
(Switch level
9
on)
Light Level
6 (600)
Lux off level
(Switch level
9
off)
Load type
DALI
Sensitivity
9
Defaults
Burn-in
0
(Hours)
Presence /
Presence
Presence
Absence
Shift
All manuals and user guides at all-guides.com
Number of shift
0
1
2
SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2
Cancel
On
Raise
overide on
Cancel
Off
Lower
overide off
On
Off
5, 15, 30
1
(5, 15, 30
(10 seconds)
minutes)
2, 5 & 7
4, 6 & 9
2 (200)
5 (500)
7 (700)
2, 5 & 7
4, 6 & 9
2 (Dali)
7 (DSI)
1, 5 & 9
3, 6 & 8
D
0
50
100
Absence
presses
3
UHS5 Handset Graphics Description
SHIFT 1 SHIFT 2
4 (400)
6 (600)
9 (999)
2 (D-ON)
Turn lights on or to raise lights.
Turn lights off or to lower lights.
When set to On this causes a red LED to
flash on the sensor when it detects
movement. Use this feature to check for
adequate sensitivity levels.
Once the detector is turned on, this
value sets how long the lights will stay
on once movement has ceased.
Lux level setting to prevent the
luminaires being switched on if the
ambient light level is sufficient
(adjustable between 1 and 9). The
luminaires will always be switched on at
level 9.
Sets a target light level to be maintained
by the lighting system. 9 (999) =
disabled.
Lux level setting switches the luminaires
off during occupancy if the ambient light
level goes above the setting (adjustable
between 1 and 9). Level 9 will always
keep the lights on. This setting can be
used for "window row switching". Note:
the Lux Off Level value must always be
greater than the Lux On Level value.
Sets the ballast control protocol to be
used by the output channel.
Sensitivity level for detecting
movement.
1 = low sensitivity
9 = high sensitivity
Returns the unit to the default settings.
Determines how long the output will be
at 100% so that lamps 'burn-in'. The
'burn-in' time is not affected by power
supply interruptions.
Presence mode allows the output to
turn on when movement is detected
and off when movement ceases.
Absence mode allows the output to turn
off when movement ceases, but must
be manually turned on first.
Use this button to select the settings in
red and blue signified by the 'Shift 1' and
'Shift 2' LEDs