IZAR RECEIVER M-Bus
4.
Technical data
General
Power supply (via M-Bus) U = 32 V ... 42 V Imax =
Housing
Weight
Environment
Protection class
Operating temperature
range
Relative humidity
5.
Instructions
The IZAR RECEIVER M-Bus should be mounted
and put into operation by qualified experts only.
When installing suitable preventive measures for
EMC protection must be met.
Please ensure that the M-Bus voltage - depend-
ing on the cable length (resistance and imped-
ance) is never below 32 V, in order to operate the
IZAR RECEIVER M-Bus.
- 12 -
30 mA (20 M-Bus loads)
120 x 120 x 35 mm plastic
housing for wall mounting
(internal antenna)
approx. 200 g
IP 20
0 °C ... +60 °C
10 % ... 70 % relative
humidity, non-condensing